Powerware 9305 UPS 

Powerware 9330

Special features
 
bullet

Maximum Availability - true double conversion online design, the proven technology that is used for the most mission-critical applications in the world. It's virtually impossible to find line-interactive, pseudo-online or any other kind of UPS other than double conversion online supporting 24/365 data centers, facilities, ISPs and major telecommunications installations.

bulletMaximum Reliability - with Powerware Hot Sync, the award-winning, patented technology that achieves paralleling for redundancy and capacity (up to four modules) with no system-level single-point-of-failure. The preferred paralleling technology installed around the world with such major customers as ETrade, Colo.com, and Citibank, Powerware Hot Sync will be available in the 10-40 kVA range mid-2001 with the Powerware 9330.
bullet

Maximum Efficiency - the Powerware 9330's advanced design features the highest level of efficiency of any double conversion online UPS with 96% efficiency, at rated kVA and power factor. That number increases to 97% with the debut of Powerware's Energy Optimizer* patented technology. No need to compromise reliability for efficiency with the Powerware 9330.
*Available mid 2001

bullet

Maximum Performance - the Powerware 9330 delivers the highest performance by using Digital Signal Processing, true Pulse-Width-Modulation and maximum IGBT responsiveness. This provides easy setup, drift-free operation and a pristine output signal.

bullet

Global Services - Powerware service professionals provide round-the-clock monitoring, remote diagnostics, and on-site maintenance programs. More than just a material warranty, this is the most comprehensive service coverage available in the industry. Powerware Global Service provides our customers with peace of mind that potential downtime is prevented by proactive service and monitoring.

Rating: 10, 15, 20, 25, 30, 35, 40kVA
Voltage: 208/208, 480/208, 480/480, 600/208  VAC
Frequency: 50/60 Hz
Configuration: Single Module - Reverse Transfer
Powerware Hot Sync - Redundant*
Powerware Hot Sync - Capacity*
Topology: Online

* Available mid-2001

 

 

 

Specification overview

bulletDouble Conversion Online Technology provides reliable operation
bullet True Pulse Width Modulation (PWM) Technology and Digital Signal Processing - increases overall system reliability and ensuring perfect power on the output.
bullet Energy Optimizer™ Mode - increases operating online efficiency from 92% up to 97%.
bullet High Efficiency - increases overall system reliability, availability and performance and equals lower overall cost of ownership. 
bullet Powerware Hot Sync™ Technology - is a paralleling system that reduces the risks of traditional UPSs by eliminating connections that can fail and shut down a critical load. Each UPS module operates independently of other modules to synchronize and support the load. Powerware Hot Sync permits the UPS to sample the output power over 3,000 times per second, adjusting and synchronizing accordingly. This unique approach to paralleling provides redundancy and capacity capability with system availability of 99.99 percent or greater.
This feature will be available for the Powerware 9330 mid-2001
bullet Battery Management System - includes  DC Expert ™, Temperature Compensated Charging (TCC) and Battery Circuit Test (BCT).
bullet Global Service - The most comprehensive service coverage available in the industry. Round-the-clock monitoring, remote diagnostics, and on-site maintenance programs provide the customer peace of mind. 
bullet Intelligent Communications & Monitoring - An extensive array of communication gives the customer the ability to mange the Powerware 9330 locally or remotely via serial or network communications.
bullet Built-in Control Area Network (CAN) assists in integrating peripherals and options, controllable from the control panel. It also reduces the internal wiring connections required therefore increasing overall system reliability.
bullet Superior Cooling Design - Keeping critical components at the coolest possible levels, ensures precise system operation and extending the life of system elements.
bullet Environmental Capabilities - efficiency combined with a well-engineered cooling design allows the UPS to reliably operate under extreme environmental conditions.
bullet Internal Maintenance Bypass - Provides the ability to quickly perform maintenance on the critical load essential to maintaining overall systems availability and reliability.
bullet Field Expandable - The Powerware 9330 provides our customers with a UPS that can grow with their system needs, whether it's to increase the kVA rating or change system configuration from a single module system to a multi-module redundant or capacity system.
bullet Comprehensive Communications and User Interface - A large LCD display and control panel is ergonomically situated for operator interface with the unit. Soft keys help guide the operator through all menus and setups. A dedicated microprocessor had been designed and engineered to provide sophisticated full featured monitoring, extensive alarm history, and additional communication options, including Ethernet, network links, and modems. The intelligent firmware controls are designed to provide maximize protection to the critical load, and prevent operator actions that might jeopardize the load, such as the Smart Load Off button.
bullet Generator Compatibility - Double-conversion online UPS technology is the only topology that can regulate frequency without transferring to battery.
bullet Dual Feed Inputs - Separate rectifier and bypass feeds are standard which increases availability by providing input feeder buses.

 

Powerware 9330

Specification details

 

Electrical Input

Input Voltage

120/208 VAC, 3 phase + GND (rectifier)
120/208 VAC, 3 phase + N + GND (Bypass)

Voltage Range

-15%, +10%

Frequency

50/60 Hz

Frequency Range

45 - 65 Hz

Input Power Factor

> 0.96, Typical

Surge Protection

Meets IEEE 587, Category A & B and EN 50091-2 

Electrical Output

Output Voltage

120/208

Voltage Regulation

Static: better than ±1%
Dynamic: better than Figure one of EN50091-3 (IEC 62040-3)

Voltage Distortion 

Less than 3% for 100% linear load
Less than 5% for nonlinear load when tested in accordance with EN50091-3

Frequency Regulation

Synchronization: ±0.5, ±1.0, ±2.0 Hz, selectable
Free-running: ±0.005 Hz
Slew rate: 0.5, 1.0, 2.0, 3.0 Hz / sec, max selectable

Over Current

101 - 110% for 10 min (inverter)
111 - 125% for 1 min (inverter)
126 - 150% for 30 sec (inverter)

Environmental

Ambient Temperature

Operation 0 to + 40ºC (32 to 104ºF)
Storage -20 to 70ºC (-4 to 140ºF)

Relative Humidity

95% maximum, non-condensing

Altitude

1500 meters (5000ft) at 40ºC ambient without load derating

Audible noise

Less than 55dBA typical at 1 meter; in accordance with ISO 7779

Electrostatic Discharge

Withstands 25kV without damage or disturbance to the load; exceeds requirements of IEC 801-2

EMC

Meets FCC Class A and EN50091-2 (IEC 62040-2)

Safety

 

UL1778
CUL CAN/CSA C22.2 NO.107.1
EN 50091-1

Mechanical

Cable Entry

Bottom rear, Bottom front

Cooling

Filtered forced air with redundant fans

Access

Front and top only required for service

Communications

Serial Port

RS-232 communications port standard

Service Port

RS-232 for service of equipment by qualified service personnel standard

Communication Cards

up to four optional cards can be installed in the UPS module at any time and provide the following connectivity:
– single RS-232 port
– multiple RS-232 ports
– Ethernet Interface
– SNMP Adapter
– Modem Driver

Remote Communications

Four input building alarm contacts
Two summary alarm contacts

Relay Interface Module

Optional– provides five relay contacts


Model Selection Guide

POWERWARE 9330-20
PERFORMANCE CHARACTERISTICS
 

MODEL 10
10KVA/7KW

MODEL 15
15KVA/10.5KW

MODEL 20
20KVA/14KW

Input Voltage Volts 208 480 480 600  208 480 480  600 208 480 480  600 
Output Voltage Volts 208  208  480  208  208  208  480  208  208  208  480  208 
Input/output Frequency Hz 50/60 60  60   60 50/60 60  60   60 50/60 60  60   60
Input Voltage Range        
Minimum Volts 177  408  408  510  177  408  408  510  177  408  408  510 
Maximum Volts 228  528  528  660  228  528  528  660  228  528  528  660 
AC Input (With input filter)        
Nominal Amps 22  10  10  32  14  15  11  43  19  20  15 
Maximum Amps 29  13  13  10  40  18  18  15  51  23  23  19 
Bypass Input        
Nominal Amps Amps 28  12  12  10  42  18  18  14  56  24  24  19 
AC Output        
Nominal Amps Amps 28  28  12  28  42  42  18  42  56  56  24  56 
10 Minutes Amps 35  35  15  35  52  52  23  52  69  69  30  69 
Battery        
Nominal Voltage Volts 288  288  288  288  288  288  288  288  288  288  288  288 
Float Voltage @ 25ºC  Volts 336  336  336  336  336  336  336  336  336  336  336  336 
Charge Current   Amps
Nominal Discharge Current  Amps 26  26  26  26  39  39  39  39  39  39  39  39 
Total Cell Count   144  144  144  144  144  144  144  144  144  144  144  144 
System Efficiency1        
@100%Load   91% 88% 86% 86%  92% 89% 87% 87% 92%  90% 88% 90%
@75%Load   90% 87%  85%  85% 92% 89% 86% 86% 92% 90% 88% 90%
@50%Load     88% 85% 83% 83% 91% 88% 85% 85% 92%  90% 88% 90%
.7pf@100%Load     96% 93% 91% 93% 96% 94% 92% 94% 96%  94% 92% 94%
Max. Heat Dissipation        

BTU/Hr.(x1000) 

  3.3 4.2 4.8 4.8 4.1 5.4 6.3 6.3 5.1 6.3 7.5 6.3

kcal/Hr.(x1000)

  0.8 1.1 1.2 1.2 1.0 1.4 1.6  1.6 1.3 1.6 1.9 1.6
Inverter Efficiency (Full Load) %  93% 93% 90% 93%  94% 94% 92% 94% 94% 94% 92% 94%
Physical Attributes (max.)        

Width

inches 22 39  39 39  22  39  39  39  22  39  39  39 

1) Efficiency shown takes into account the output transformer for input or output voltages other then 208V

POWERWARE 9330-40
PERFORMANCE CHARACTERISTICS
 

MODEL 25
25KVA/17.5KW

MODEL 30
30KVA/21KW

MODEL 35
35KVA/24.5KW

MODEL 40
40KVA/28KW

Input Voltage Volts 208 480 480 600  208 480 480  600 208 480 480  600  208 480 480  600 
Output Voltage Volts 208  208  480  208  208  208  480  208  208  208  480  208  208  208  480  208 
Input/output Frequency Hz 50/60 60  60   60 50/60 60  60   60 50/60 60  60   60 50/60 60  60   60
Input Voltage Range          
Minimum Volts 177  408  408  510  177  408  408  510  177  408  408  510  177  408  408  510 
Maximum Volts 229  528  528  660  229  528  528  660  229  528  528  660  229  528  528  660 
AC Input          
Nominal Amps 55  24  24  19  66  29  29  23  77  34  34  27  82  38  38  30 
Maximum Amps 70  30  30  24  83  36  36  29  97  42  42  34  100  48  48  38 
Bypass Input          
Nominal Amps Amps 69  30  30  24  83  36  36  29  97  42  42  34  111  48  48