Back Up Next Home Batteries  UPS Technology Emergency Lighting Battery Chargers Factory Links Contact Us Buy Batteries Online

Established 1996                              Call us 800-706-7009

.
Home GE Digital Energy LPC Powerware MGE Liebert MinuteMan ONEAC White Papers Remote Monitoring

.

 

Click here to Buy batteries online

Batteries
UPS Technology
Emergency Lighting
Battery Chargers
TVSS
9 Power Problems
Problems with Power
Factory Links
Contact Us

Powerware Manuals
PW3105
PW3110
PW5110
PW5115 Tower
PW5115 Rack
Evolution
Evolution S
PW5119
PW5125 Tower
PW5125 Rack/Tower
PW5130
PW5140
PW9104
PW9120
PW9125
EX Tower
EX Rack/Tower
PW9130 Tower
PW9130 Rack
PW9135
PW9140
PW9150
PW9155
PW9170
PW9170+
Prestige
Ferrups
BladeUPS
PW9305
PW9315
PW9330
PW9355
PW9390
Plus 18
Plus 36
IPK-0329

 

Powerware 9305 UPS

Contact us @ 800-706-7009 or click here for more information. 

Powerware 9330

Special features
 
  • Maximum Availability - true double conversion online design, the proven technology that is used for the most mission-critical applications in the world. It's virtually impossible to find line-interactive, pseudo-online or any other kind of UPS other than double conversion online supporting 24/365 data centers, facilities, ISPs and major telecommunications installations.

  • Maximum Reliability - with Powerware Hot Sync, the award-winning, patented technology that achieves paralleling for redundancy and capacity (up to four modules) with no system-level single-point-of-failure. The preferred paralleling technology installed around the world with such major customers as ETrade, Colo.com, and Citibank, Powerware Hot Sync will be available in the 10-40 kVA range mid-2001 with the Powerware 9330.
  • Maximum Efficiency - the Powerware 9330's advanced design features the highest level of efficiency of any double conversion online UPS with 96% efficiency, at rated kVA and power factor. That number increases to 97% with the debut of Powerware's Energy Optimizer* patented technology. No need to compromise reliability for efficiency with the Powerware 9330.
    *Available mid 2001

  • Maximum Performance - the Powerware 9330 delivers the highest performance by using Digital Signal Processing, true Pulse-Width-Modulation and maximum IGBT responsiveness. This provides easy setup, drift-free operation and a pristine output signal.

  • Global Services - Powerware service professionals provide round-the-clock monitoring, remote diagnostics, and on-site maintenance programs. More than just a material warranty, this is the most comprehensive service coverage available in the industry. Powerware Global Service provides our customers with peace of mind that potential downtime is prevented by proactive service and monitoring.

Rating: 10, 15, 20, 25, 30, 35, 40kVA
Voltage: 208/208, 480/208, 480/480, 600/208  VAC
Frequency: 50/60 Hz
Configuration: Single Module - Reverse Transfer
Powerware Hot Sync - Redundant*
Powerware Hot Sync - Capacity*
Topology: Online

* Available mid-2001

 

 

 

Specification overview

  • Double Conversion Online Technology provides reliable operation
  • True Pulse Width Modulation (PWM) Technology and Digital Signal Processing - increases overall system reliability and ensuring perfect power on the output.
  • Energy Optimizer™ Mode - increases operating online efficiency from 92% up to 97%.
  • High Efficiency - increases overall system reliability, availability and performance and equals lower overall cost of ownership. 
  • Powerware Hot Sync™ Technology - is a paralleling system that reduces the risks of traditional UPSs by eliminating connections that can fail and shut down a critical load. Each UPS module operates independently of other modules to synchronize and support the load. Powerware Hot Sync permits the UPS to sample the output power over 3,000 times per second, adjusting and synchronizing accordingly. This unique approach to paralleling provides redundancy and capacity capability with system availability of 99.99 percent or greater.
    This feature will be available for the Powerware 9330 mid-2001
  • Battery Management System - includes  DC Expert ™, Temperature Compensated Charging (TCC) and Battery Circuit Test (BCT).
  • Global Service - The most comprehensive service coverage available in the industry. Round-the-clock monitoring, remote diagnostics, and on-site maintenance programs provide the customer peace of mind. 
  • Intelligent Communications & Monitoring - An extensive array of communication gives the customer the ability to mange the Powerware 9330 locally or remotely via serial or network communications.
  • Built-in Control Area Network (CAN) assists in integrating peripherals and options, controllable from the control panel. It also reduces the internal wiring connections required therefore increasing overall system reliability.
  • Superior Cooling Design - Keeping critical components at the coolest possible levels, ensures precise system operation and extending the life of system elements.
  • Environmental Capabilities - efficiency combined with a well-engineered cooling design allows the UPS to reliably operate under extreme environmental conditions.
  • Internal Maintenance Bypass - Provides the ability to quickly perform maintenance on the critical load essential to maintaining overall systems availability and reliability.
  • Field Expandable - The Powerware 9330 provides our customers with a UPS that can grow with their system needs, whether it's to increase the kVA rating or change system configuration from a single module system to a multi-module redundant or capacity system.
  • Comprehensive Communications and User Interface - A large LCD display and control panel is ergonomically situated for operator interface with the unit. Soft keys help guide the operator through all menus and setups. A dedicated microprocessor had been designed and engineered to provide sophisticated full featured monitoring, extensive alarm history, and additional communication options, including Ethernet, network links, and modems. The intelligent firmware controls are designed to provide maximize protection to the critical load, and prevent operator actions that might jeopardize the load, such as the Smart Load Off button.
  • Generator Compatibility - Double-conversion online UPS technology is the only topology that can regulate frequency without transferring to battery.
  • Dual Feed Inputs - Separate rectifier and bypass feeds are standard which increases availability by providing input feeder buses.

 

Powerware 9330

Specification details

 

Electrical Input

Input Voltage

120/208 VAC, 3 phase + GND (rectifier)
120/208 VAC, 3 phase + N + GND (Bypass)

Voltage Range

-15%, +10%

Frequency

50/60 Hz

Frequency Range

45 - 65 Hz

Input Power Factor

> 0.96, Typical

Surge Protection

Meets IEEE 587, Category A & B and EN 50091-2 

Electrical Output

Output Voltage

120/208

Voltage Regulation

Static: better than ±1%
Dynamic: better than Figure one of EN50091-3 (IEC 62040-3)

Voltage Distortion 

Less than 3% for 100% linear load
Less than 5% for nonlinear load when tested in accordance with EN50091-3

Frequency Regulation

Synchronization: ±0.5, ±1.0, ±2.0 Hz, selectable
Free-running: ±0.005 Hz
Slew rate: 0.5, 1.0, 2.0, 3.0 Hz / sec, max selectable

Over Current

101 - 110% for 10 min (inverter)
111 - 125% for 1 min (inverter)
126 - 150% for 30 sec (inverter)

Environmental

Ambient Temperature

Operation 0 to + 40ºC (32 to 104ºF)
Storage -20 to 70ºC (-4 to 140ºF)

Relative Humidity

95% maximum, non-condensing

Altitude

1500 meters (5000ft) at 40ºC ambient without load derating

Audible noise

Less than 55dBA typical at 1 meter; in accordance with ISO 7779

Electrostatic Discharge

Withstands 25kV without damage or disturbance to the load; exceeds requirements of IEC 801-2

EMC

Meets FCC Class A and EN50091-2 (IEC 62040-2)

Safety

 

UL1778
CUL CAN/CSA C22.2 NO.107.1
EN 50091-1

Mechanical

Cable Entry

Bottom rear, Bottom front

Cooling

Filtered forced air with redundant fans

Access

Front and top only required for service

Communications

Serial Port

RS-232 communications port standard

Service Port

RS-232 for service of equipment by qualified service personnel standard

Communication Cards

up to four optional cards can be installed in the UPS module at any time and provide the following connectivity:
– single RS-232 port
– multiple RS-232 ports
– Ethernet Interface
– SNMP Adapter
– Modem Driver

Remote Communications

Four input building alarm contacts
Two summary alarm contacts

Relay Interface Module

Optional– provides five relay contacts


Model Selection Guide

POWERWARE 9330-20
PERFORMANCE CHARACTERISTICS
 

MODEL 10
10KVA/7KW

MODEL 15
15KVA/10.5KW

MODEL 20
20KVA/14KW

Input Voltage Volts 208 480 480 600  208 480 480  600 208 480 480  600 
Output Voltage Volts 208  208  480  208  208  208  480  208  208  208  480  208 
Input/output Frequency Hz 50/60 60  60   60 50/60 60  60   60 50/60 60  60   60
Input Voltage Range        
Minimum Volts 177  408  408  510  177  408  408  510  177  408  408  510 
Maximum Volts 228  528  528  660  228  528  528  660  228  528  528  660 
AC Input (With input filter)        
Nominal Amps 22  10  10  32  14  15  11  43  19  20  15 
Maximum Amps 29  13  13  10  40  18  18  15  51  23  23  19 
Bypass Input        
Nominal Amps Amps 28  12  12  10  42  18  18  14  56  24  24  19 
AC Output        
Nominal Amps Amps 28  28  12  28  42  42  18  42  56  56  24  56 
10 Minutes Amps 35  35  15  35  52  52  23  52  69  69  30  69 
Battery        
Nominal Voltage Volts 288  288  288  288  288  288  288  288  288  288  288  288 
Float Voltage @ 25ºC  Volts 336  336  336  336  336  336  336  336  336  336  336  336 
Charge Current   Amps
Nominal Discharge Current  Amps 26  26  26  26  39  39  39  39  39  39  39  39 
Total Cell Count   144  144  144  144  144  144  144  144  144  144  144  144 
System Efficiency1        
@100%Load   91% 88% 86% 86%  92% 89% 87% 87% 92%  90% 88% 90%
@75%Load   90% 87%  85%  85% 92% 89% 86% 86% 92% 90% 88% 90%
@50%Load     88% 85% 83% 83% 91% 88% 85% 85% 92%  90% 88% 90%
.7pf@100%Load     96% 93% 91% 93% 96% 94% 92% 94% 96%  94% 92% 94%
Max. Heat Dissipation        

BTU/Hr.(x1000) 

  3.3 4.2 4.8 4.8 4.1 5.4 6.3 6.3 5.1 6.3 7.5 6.3

kcal/Hr.(x1000)

  0.8 1.1 1.2 1.2 1.0 1.4 1.6  1.6 1.3 1.6 1.9 1.6
Inverter Efficiency (Full Load) %  93% 93% 90% 93%  94% 94% 92% 94% 94% 94% 92% 94%
Physical Attributes (max.)        

Width

inches 22 39  39 39  22  39  39  39  22  39  39  39 

1) Efficiency shown takes into account the output transformer for input or output voltages other then 208V

POWERWARE 9330-40
PERFORMANCE CHARACTERISTICS
 

MODEL 25
25KVA/17.5KW

MODEL 30
30KVA/21KW

MODEL 35
35KVA/24.5KW

MODEL 40
40KVA/28KW

Input Voltage Volts 208 480 480 600  208 480 480  600 208 480 480  600  208 480 480  600 
Output Voltage Volts 208  208  480  208  208  208  480  208  208  208  480  208  208  208  480  208 
Input/output Frequency Hz 50/60 60  60   60 50/60 60  60   60 50/60 60  60   60 50/60 60  60   60
Input Voltage Range          
Minimum Volts 177  408  408  510  177  408  408  510  177  408  408  510  177  408  408  510 
Maximum Volts 229  528  528  660  229  528  528  660  229  528  528  660  229  528  528  660 
AC Input          
Nominal Amps 55  24  24  19  66  29  29  23  77  34  34  27  82  38  38  30 
Maximum Amps 70  30  30  24  83  36  36  29  97  42  42  34  100  48  48  38 
Bypass Input          
Nominal Amps Amps 69  30  30  24  83  36  36  29  97  42  42  34  111  48  48  38 
AC Output          
Nominal Amps Amps 69  69  30  69  83  83  36  84  97  97  42  96  111  111  48  112 
10 Minutes Amps 86  86  38  86  104  104  45  105  121  121  53  120  139  139  60  140 
Battery          
Nominal Voltage Volts 288  288  288  288  288  288  288  288  288  288  288  288  288  288  288  288 
Float Voltage @ 25ºC  Volts 336  336  336  336  336  336  336  336  336  336  336  336  336  336  336  336 
Charge Current   Amps
Nominal Discharge Current  Amps 64  64  64  64  78  78  78  78  91  91  91  91  100  100  100  100 
System Efficiency1          
@100%Load   92% 90% 88% 90%  92% 90% 88% 90% 92%  90% 88% 90% 93%  91% 89% 91%
@75%Load   91% 89%  87%  89% 92% 90% 88% 90% 92% 90% 88% 90% 92% 90% 88% 90%
@50%Load     89% 87% 85% 87% 91% 89% 87% 89% 91%  89% 87% 89% 92%  90% 88% 90%
.7pf@100%Load     97% 93% 91% 93% 96% 94% 92% 94% 96%  94% 92% 94% 96%  94% 92% 94%
Max. Heat Dissipation          

BTU/Hr.(x1000) 

  4.8 6.0 7.2 6.0 5.7 7.2 8.6 7.2 6.7 8.4 10.0 8.4 6.7 8.6 10.5 8.6

kcal/Hr.(x1000)

  1.2 1.5 1.8 1.5 1.4 1.8 2.2  1.8 1.7 2.1 2.5 2.1 1.7 2.2 2.6 2.2
Inverter Efficiency (Full Load) %  93% 93% 91% 93%  93% 93% 91% 93% 93% 93% 91% 93% 94% 94% 92% 94%
Physical Attributes (max.)          

Width

inches 39 61  61 61  39  61  61  61  39  61  61  61  39  61  61  61 

Height

inches 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45

Depth1

inches 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31

1) Efficiency shown takes into account the output transformer for input or output voltages other then 208V

2 All accessories feature plug and play capability.
Shipping pallet and packaging adds 50 lbs. per shipping unit.

3 Options cabinet is required for voltages other than
208/208 V In/Out.

2

3

 

 UPS Battery Run Times (in minutes)

 

9330-20 Series 9330-40 Series
  Model 10
10kVa
7kW
Model 15
15kVa
10.5kW
Model 20
20kVa
14kW
Model 25
25kVak
17.5kW
Model 30
30kVa
21kW
Model 35
35kVa
24.5kW
Model 40
40kVa
28kW

Base Unit

35 20 12 26 20 15 12

+1 Battery Cabinet

95 50 35 49 38 33 26

+2 Battery Cabinets

150 95 60 64 50 44 35

+3 Battery Cabinets

200 130 95 98 76 62 49

+4 Battery Cabinets

n/a n/a n/a 122 95 75 60

+5 Battery Cabinets

n/a n/a n/a 146 114 100 79

Powerware 9305 UPS  Powerware 9305 UPS  Powerware 9305 UPS  Powerware 9305 UPS  Powerware 9305 UPS  Powerware 9305 UPS  Powerware 9305 UPS 

 

Home Batteries  UPS Technology Emergency Lighting Battery Chargers Factory Links Contact Us Buy Batteries Online

Power Factor Inc.

2526 Manana Dr – Suite 102 – Dallas – Texas – 75220

800-706-7009

 Our Goal, NO DISSATISFIED CUSTOMERS!

Since 1995

While every precaution has been taken to ensure accuracy and completeness in this literature, Power Factor Inc. assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.