Powerware Manuals PW3105 PW3110 PW5110 PW5115 Tower PW5115 Rack Evolution Evolution S PW5119 PW5125 Tower PW5125 Rack/Tower PW5130 PW5140 PW9104 PW9120 PW9125 EX Tower EX Rack/Tower PW9130 Tower PW9130 Rack PW9135 PW9140 PW9150 PW9155 PW9170 PW9170+ Prestige Ferrups BladeUPS PW9305 PW9315 PW9330 PW9355 PW9390 Plus 18 Plus 36 IPK-0329
| |

Powerware 9305 UPS



-
Maximum
Availability - true double conversion online design, the proven
technology that is used for the most mission-critical applications in the
world. It's virtually impossible to find line-interactive, pseudo-online
or any other kind of UPS other than double conversion online supporting
24/365 data centers, facilities, ISPs and major telecommunications
installations.
- Maximum
Reliability - with Powerware Hot Sync, the award-winning, patented
technology that achieves paralleling for redundancy and capacity (up to
four modules) with no system-level single-point-of-failure. The preferred
paralleling technology installed around the world with such major
customers as ETrade, Colo.com, and Citibank,
Powerware Hot Sync will be available in the 10-40 kVA range mid-2001 with
the Powerware 9330.
-
Maximum
Efficiency - the Powerware 9330's advanced design features the highest
level of efficiency of any double conversion online UPS with 96%
efficiency, at rated kVA and power factor. That number increases to 97%
with the debut of Powerware's Energy Optimizer* patented technology. No
need to compromise reliability for efficiency with the Powerware 9330.
*Available mid 2001
-
Maximum
Performance - the Powerware 9330 delivers the highest performance by
using Digital Signal Processing, true Pulse-Width-Modulation and maximum
IGBT responsiveness. This provides easy setup, drift-free operation and a
pristine output signal.
-
Global Services
- Powerware service professionals provide round-the-clock monitoring,
remote diagnostics, and on-site maintenance programs. More than just a
material warranty, this is the most comprehensive service coverage
available in the industry. Powerware Global Service provides our customers
with peace of mind that potential downtime is prevented by proactive
service and monitoring.
|
Rating: |
10, 15, 20, 25, 30,
35, 40kVA |
|
Voltage: |
208/208, 480/208,
480/480, 600/208 VAC |
|
Frequency: |
50/60 Hz |
|
Configuration: |
Single Module -
Reverse Transfer
Powerware Hot Sync - Redundant*
Powerware Hot Sync - Capacity* |
|
Topology: |
Online |
* Available mid-2001 |
|

- Double Conversion
Online Technology provides reliable operation
-
True Pulse Width Modulation (PWM) Technology and Digital Signal Processing
- increases overall system reliability and ensuring perfect power on
the output.
-
Energy Optimizer™ Mode
- increases operating online efficiency from 92% up to 97%.
-
High Efficiency
- increases overall system reliability, availability and performance
and equals lower overall cost of ownership.
-
Powerware Hot Sync™ Technology -
is a paralleling system
that reduces the risks of traditional UPSs by eliminating connections that can
fail and shut down a critical load. Each UPS module operates independently of
other modules to synchronize and support the load. Powerware Hot Sync permits
the UPS to sample the output power over 3,000 times per second, adjusting and
synchronizing accordingly. This unique approach to paralleling provides
redundancy and capacity capability with system availability of 99.99 percent
or greater.
This feature will be available for the Powerware 9330 mid-2001
-
Battery Management System
- includes DC
Expert ™, Temperature Compensated Charging (TCC) and Battery Circuit Test (BCT).
-
Global Service -
The most comprehensive service coverage available in the industry.
Round-the-clock monitoring, remote diagnostics, and on-site maintenance
programs provide the customer peace of mind.
-
Intelligent Communications & Monitoring
- An extensive array of communication
gives the customer the ability to mange the Powerware 9330 locally or
remotely via serial or network communications.
-
Built-in Control Area Network (CAN) - assists in integrating
peripherals and options, controllable from the control panel. It also reduces
the internal wiring connections required therefore increasing overall system
reliability.
-
Superior Cooling Design - Keeping critical components at the
coolest possible levels, ensures precise system operation and extending the
life of system elements.
-
Environmental Capabilities - efficiency combined with a well-engineered
cooling design allows the UPS to reliably operate under extreme environmental
conditions.
-
Internal Maintenance Bypass - Provides the ability to quickly perform
maintenance on the critical load essential to maintaining overall systems
availability and reliability.
-
Field Expandable - The Powerware 9330 provides our customers
with a UPS that can grow with their system needs, whether it's to increase the
kVA rating or change system configuration from a single module system to a
multi-module redundant or capacity system.
-
Comprehensive Communications and User Interface
- A large LCD display and control panel is ergonomically situated for
operator interface with the unit. Soft keys help guide the operator through
all menus and setups. A dedicated microprocessor had been designed and
engineered to provide sophisticated full featured monitoring, extensive alarm
history, and additional communication options, including Ethernet, network
links, and modems. The intelligent firmware controls are designed to provide
maximize protection to the critical load, and prevent operator actions that
might jeopardize the load, such as the Smart Load Off button.
-
Generator Compatibility
- Double-conversion online UPS technology is the only topology that can
regulate frequency without transferring to battery.
-
Dual Feed Inputs - Separate rectifier and bypass feeds are standard which
increases availability by providing input feeder buses.



|
Electrical Input |
|
Input
Voltage |
120/208 VAC, 3 phase + GND (rectifier)
120/208 VAC, 3 phase + N + GND (Bypass) |
|
Voltage
Range |
-15%, +10% |
|
Frequency |
50/60
Hz |
|
Frequency
Range |
45 - 65 Hz |
|
Input
Power Factor |
>
0.96, Typical |
|
Surge
Protection |
Meets IEEE
587, Category A & B and EN 50091-2 |
|
Electrical Output |
|
Output
Voltage |
120/208 |
|
Voltage
Regulation |
Static:
better than ±1%
Dynamic: better than Figure one of EN50091-3 (IEC 62040-3) |
|
Voltage
Distortion |
Less
than 3% for 100% linear load
Less than 5% for nonlinear load when tested in accordance with
EN50091-3 |
|
Frequency
Regulation |
Synchronization: ±0.5, ±1.0, ±2.0 Hz, selectable
Free-running: ±0.005 Hz
Slew rate: 0.5, 1.0, 2.0, 3.0 Hz / sec, max selectable |
|
Over
Current |
101 - 110% for 10 min (inverter)
111 - 125% for 1 min (inverter)
126 - 150% for 30 sec (inverter) |
|
Environmental |
|
Ambient
Temperature |
Operation
0 to + 40ºC (32 to 104ºF)
Storage -20 to 70ºC (-4 to 140ºF) |
|
Relative
Humidity |
95%
maximum, non-condensing |
|
Altitude |
1500
meters (5000ft) at 40ºC ambient without load derating |
|
Audible
noise |
Less than
55dBA typical at 1 meter; in accordance with ISO 7779 |
|
Electrostatic Discharge |
Withstands
25kV without damage or disturbance to the load; exceeds
requirements of IEC 801-2 |
|
EMC |
Meets FCC
Class A and EN50091-2 (IEC 62040-2) |
|
Safety |
|
|
UL1778
CUL CAN/CSA C22.2 NO.107.1
EN 50091-1 |
|
Mechanical |
|
Cable
Entry |
Bottom
rear, Bottom front |
|
Cooling |
Filtered
forced air with redundant fans |
|
Access |
Front
and top only required for service |
|
Communications |
|
Serial
Port |
RS-232
communications port standard |
|
Service
Port |
RS-232
for service of equipment by qualified service personnel
standard |
|
Communication Cards |
up to four
optional cards can be installed in the UPS module at any time
and provide the following connectivity:
– single RS-232 port
– multiple RS-232 ports
– Ethernet Interface
– SNMP Adapter
– Modem Driver |
|
Remote
Communications |
Four
input building alarm contacts
Two summary alarm contacts |
|
Relay
Interface Module |
Optional–
provides five relay contacts |
Model Selection Guide
POWERWARE 9330-20
PERFORMANCE CHARACTERISTICS |
|
MODEL 10
10KVA/7KW |
MODEL 15
15KVA/10.5KW |
MODEL 20
20KVA/14KW |
|
Input Voltage |
Volts |
208 |
480 |
480 |
600 |
208 |
480 |
480 |
600 |
208 |
480 |
480 |
600 |
|
Output Voltage |
Volts |
208 |
208 |
480 |
208 |
208 |
208 |
480 |
208 |
208 |
208 |
480 |
208 |
|
Input/output Frequency |
Hz |
50/60 |
60 |
60 |
60 |
50/60 |
60 |
60 |
60 |
50/60 |
60 |
60 |
60 |
|
Input
Voltage Range |
|
|
|
|
|
Minimum |
Volts |
177 |
408 |
408 |
510 |
177 |
408 |
408 |
510 |
177 |
408 |
408 |
510 |
|
Maximum |
Volts |
228 |
528 |
528 |
660 |
228 |
528 |
528 |
660 |
228 |
528 |
528 |
660 |
|
AC Input
(With input filter) |
|
|
|
|
|
Nominal |
Amps |
22 |
10 |
10 |
8 |
32 |
14 |
15 |
11 |
43 |
19 |
20 |
15 |
|
Maximum |
Amps |
29 |
13 |
13 |
10 |
40 |
18 |
18 |
15 |
51 |
23 |
23 |
19 |
|
Bypass
Input |
|
|
|
|
|
Nominal Amps |
Amps |
28 |
12 |
12 |
10 |
42 |
18 |
18 |
14 |
56 |
24 |
24 |
19 |
|
AC
Output |
|
|
|
|
|
Nominal
Amps |
Amps |
28 |
28 |
12 |
28 |
42 |
42 |
18 |
42 |
56 |
56 |
24 |
56 |
|
10
Minutes |
Amps |
35 |
35 |
15 |
35 |
52 |
52 |
23 |
52 |
69 |
69 |
30 |
69 |
|
Battery |
|
|
|
|
|
Nominal
Voltage |
Volts |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
|
Float
Voltage @ 25ºC |
Volts |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
|
Charge
Current |
Amps |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
|
Nominal
Discharge Current |
Amps |
26 |
26 |
26 |
26 |
39 |
39 |
39 |
39 |
39 |
39 |
39 |
39 |
|
Total
Cell Count |
|
144 |
144 |
144 |
144 |
144 |
144 |
144 |
144 |
144 |
144 |
144 |
144 |
|
System
Efficiency1 |
|
|
|
|
|
@100%Load |
|
91% |
88% |
86% |
86% |
92% |
89% |
87% |
87% |
92% |
90% |
88% |
90% |
|
@75%Load |
|
90% |
87% |
85% |
85% |
92% |
89% |
86% |
86% |
92% |
90% |
88% |
90% |
|
@50%Load |
|
88% |
85% |
83% |
83% |
91% |
88% |
85% |
85% |
92% |
90% |
88% |
90% |
|
.7pf@100%Load |
|
96% |
93% |
91% |
93% |
96% |
94% |
92% |
94% |
96% |
94% |
92% |
94% |
|
Max.
Heat Dissipation |
|
|
|
|
|
BTU/Hr.(x1000) |
|
3.3 |
4.2 |
4.8 |
4.8 |
4.1 |
5.4 |
6.3 |
6.3 |
5.1 |
6.3 |
7.5 |
6.3 |
|
kcal/Hr.(x1000) |
|
0.8 |
1.1 |
1.2 |
1.2 |
1.0 |
1.4 |
1.6 |
1.6 |
1.3 |
1.6 |
1.9 |
1.6 |
|
Inverter Efficiency (Full Load) |
% |
93% |
93% |
90% |
93% |
94% |
94% |
92% |
94% |
94% |
94% |
92% |
94% |
|
Physical
Attributes (max.) |
|
|
|
|
|
Width |
inches |
22 |
39 |
39 |
39 |
22 |
39 |
39 |
39 |
22 |
39 |
39 |
39 |
1)
Efficiency shown takes into account the output transformer for input
or output voltages other then 208V
POWERWARE 9330-40
PERFORMANCE CHARACTERISTICS |
|
MODEL 25
25KVA/17.5KW |
MODEL 30
30KVA/21KW |
MODEL 35
35KVA/24.5KW |
MODEL 40
40KVA/28KW |
|
Input Voltage |
Volts |
208 |
480 |
480 |
600 |
208 |
480 |
480 |
600 |
208 |
480 |
480 |
600 |
208 |
480 |
480 |
600 |
|
Output Voltage |
Volts |
208 |
208 |
480 |
208 |
208 |
208 |
480 |
208 |
208 |
208 |
480 |
208 |
208 |
208 |
480 |
208 |
|
Input/output Frequency |
Hz |
50/60 |
60 |
60 |
60 |
50/60 |
60 |
60 |
60 |
50/60 |
60 |
60 |
60 |
50/60 |
60 |
60 |
60 |
|
Input
Voltage Range |
|
|
|
|
|
|
Minimum |
Volts |
177 |
408 |
408 |
510 |
177 |
408 |
408 |
510 |
177 |
408 |
408 |
510 |
177 |
408 |
408 |
510 |
|
Maximum |
Volts |
229 |
528 |
528 |
660 |
229 |
528 |
528 |
660 |
229 |
528 |
528 |
660 |
229 |
528 |
528 |
660 |
|
AC Input |
|
|
|
|
|
|
Nominal |
Amps |
55 |
24 |
24 |
19 |
66 |
29 |
29 |
23 |
77 |
34 |
34 |
27 |
82 |
38 |
38 |
30 |
|
Maximum |
Amps |
70 |
30 |
30 |
24 |
83 |
36 |
36 |
29 |
97 |
42 |
42 |
34 |
100 |
48 |
48 |
38 |
|
Bypass
Input |
|
|
|
|
|
|
Nominal Amps |
Amps |
69 |
30 |
30 |
24 |
83 |
36 |
36 |
29 |
97 |
42 |
42 |
34 |
111 |
48 |
48 |
38 |
|
AC
Output |
|
|
|
|
|
|
Nominal
Amps |
Amps |
69 |
69 |
30 |
69 |
83 |
83 |
36 |
84 |
97 |
97 |
42 |
96 |
111 |
111 |
48 |
112 |
|
10
Minutes |
Amps |
86 |
86 |
38 |
86 |
104 |
104 |
45 |
105 |
121 |
121 |
53 |
120 |
139 |
139 |
60 |
140 |
|
Battery |
|
|
|
|
|
|
Nominal
Voltage |
Volts |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
288 |
|
Float
Voltage @ 25ºC |
Volts |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
336 |
|
Charge
Current |
Amps |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
7 |
|
Nominal
Discharge Current |
Amps |
64 |
64 |
64 |
64 |
78 |
78 |
78 |
78 |
91 |
91 |
91 |
91 |
100 |
100 |
100 |
100 |
|
System
Efficiency1 |
|
|
|
|
|
|
@100%Load |
|
92% |
90% |
88% |
90% |
92% |
90% |
88% |
90% |
92% |
90% |
88% |
90% |
93% |
91% |
89% |
91% |
|
@75%Load |
|
91% |
89% |
87% |
89% |
92% |
90% |
88% |
90% |
92% |
90% |
88% |
90% |
92% |
90% |
88% |
90% |
|
@50%Load |
|
89% |
87% |
85% |
87% |
91% |
89% |
87% |
89% |
91% |
89% |
87% |
89% |
92% |
90% |
88% |
90% |
|
.7pf@100%Load |
|
97% |
93% |
91% |
93% |
96% |
94% |
92% |
94% |
96% |
94% |
92% |
94% |
96% |
94% |
92% |
94% |
|
Max.
Heat Dissipation |
|
|
|
|
|
|
BTU/Hr.(x1000) |
|
4.8 |
6.0 |
7.2 |
6.0 |
5.7 |
7.2 |
8.6 |
7.2 |
6.7 |
8.4 |
10.0 |
8.4 |
6.7 |
8.6 |
10.5 |
8.6 |
|
kcal/Hr.(x1000) |
|
1.2 |
1.5 |
1.8 |
1.5 |
1.4 |
1.8 |
2.2 |
1.8 |
1.7 |
2.1 |
2.5 |
2.1 |
1.7 |
2.2 |
2.6 |
2.2 |
|
Inverter Efficiency (Full Load) |
% |
93% |
93% |
91% |
93% |
93% |
93% |
91% |
93% |
93% |
93% |
91% |
93% |
94% |
94% |
92% |
94% |
|
Physical
Attributes (max.) |
|
|
|
|
|
|
Width |
inches |
39 |
61 |
61 |
61 |
39 |
61 |
61 |
61 |
39 |
61 |
61 |
61 |
39 |
61 |
61 |
61 |
|
Height |
inches |
45 |
45 |
45 |
45 |
45 |
45 |
45 |
45 |
45 |
45 |
45 |
45 |
45 |
45 |
45 |
45 |
|
Depth1 |
inches |
31 |
31 |
31 |
31 |
31 |
31 |
31 |
31 |
31 |
31 |
31 |
31 |
31 |
31 |
31 |
31 |
1)
Efficiency shown takes into account the output transformer for input
or output voltages other then 208V
 |
2
All accessories feature plug and play capability.
Shipping pallet and packaging adds 50 lbs. per shipping unit.
3
Options cabinet is required for voltages other than
208/208 V In/Out.
2
3
|
UPS Battery Run Times
(in minutes)
|
|
9330-20 Series |
9330-40 Series |
| |
Model 10
10kVa
7kW |
Model 15
15kVa
10.5kW |
Model 20
20kVa
14kW |
Model 25
25kVak
17.5kW |
Model 30
30kVa
21kW |
Model 35
35kVa
24.5kW |
Model 40
40kVa
28kW |
|
Base Unit |
35 |
20 |
12 |
26 |
20 |
15 |
12 |
|
+1 Battery
Cabinet |
95 |
50 |
35 |
49 |
38 |
33 |
26 |
|
+2 Battery
Cabinets |
150 |
95 |
60 |
64 |
50 |
44 |
35 |
|
+3 Battery
Cabinets |
200 |
130 |
95 |
98 |
76 |
62 |
49 |
|
+4 Battery
Cabinets |
n/a |
n/a |
n/a |
122 |
95 |
75 |
60 |
|
+5 Battery
Cabinets |
n/a |
n/a |
n/a |
146 |
114 |
100 |
79 |
|
|
|