Universal Battery Valve Regulated Lead Acid Batteries Batteries

  Emergency Lighting

Battery chargers, rectifiers, dc power systems by SENS Battery Chargers

Click for more about the Battery Rack™ 20 with Tester (Grey) Battery Storage

Specials!

Service

Lease Info

 

Powerware 9170+ PW9170+

Home • Up • ASY-0673 • ASY-0674 • ASY-0529 • ASY-0675 • 066C030AAAAAAAI • 0660C60AAAAAAAI • 066C090AAAAAAAI • 066C120AAAAAAAI • 066C092AAAAAAAI • 066C122AAAAAAAI • BPE12BBM1A • BPE12MBB1A • BPE14BBM1A • BPE14MBB1A • BPE20BBM1A • BPE20MBB1A • PW3S3K • PW6S3K • PW6S6K • PW6S9K • PW9S9K • PW12S9K • PW12S12K • PW12S15K • PW12S18K

Powerware is a subsidiary of the Eaton Corporation. The Eaton name is synonymous with power. Power Factor Inc. has earned the status of an EPS (Eaton Power Specialists). We are very proud of this status and fully understand their product line and associated applications. Call our knowledgeable sales department @ 800-706-7009 for fast service & competitive pricing.

 

 

Powerware 9170+ , 9170, PW9170, Best Power, Axxium Pro Uninterruptible Power Systems ( UPS ) 



Special features
bulletN+X redundancy for both power and logic eliminates system level single-point-of-failure
bulletEasily scalable to adapt changing IT environments by simply adding power and /or battery modules
bulletTrue double conversion online design
bulletAdvanced Battery Management (ABM®) doubles battery service life
bullet Universal components fit in any order without affecting UPS operation
bulletComplete offering of power management software included to insure data integrity
bullet Warranty (US and Canada)
bullet2-year Limited Warranty 
bullet 10-year Pro-Rated Warranty
bullet $25,000 Load Protection Guarantee

 

Rating: 3-18kVA
Input Voltage: 200-240 VAC
Output Voltage: 100 - 127 or 208 - 240 Vac
Frequency: 50/60 Hz (auto sensing)
Configuration: Tower

Powerware 9170+

Specification details

 

Electrical input

 Voltage 208-240VAC or 200/100, 208/120, 220/110,240/120 Vac
Voltage Range 176-276V
Input Power Factor .98
Frequency 50/60 Hz (± 3Hz)

Electrical output

On Utility Voltage Regulation  ±3% of nominal
On Battery Voltage Regulation ±3% of nominal
Efficiency 88% normal operation
97% High performance (optional programmable)
Frequency Regulation  ±3 Hz online; ±0.1 Hz on battery

Communications

LCD Display 4 x 20 character backlit display, programmable
Language Support English, French, Spanish and German
Communication ports RS232, (DB9) (std)
Communication slots 2 Slots (standard)
SNMP capability SNMP/Web enabled card options
Contact Closures Relay Card option
Emergency Power off (EPO) Input for external EPO

General

Topology True online, double-conversion
Diagnostics Full system self-test on power up
UPS Bypass Automatic on overload or UPS failure
Dimensions and Weights See Model Selection Guide

Environmental and Safety

Safety Markings UL, CUL
EMC Markings FCC class A
Surge Suppression IEEE/ANSI C62.41
Audible Noise <50dBA
Ambient Operating/
Storage Temperature
0 to 40ºC (32 to 104ºF)/
-20 to 40ºC (60ºC w/o batt) -4 to 104ºF (140º F w/o batt)
Relative Humidity 50 to 90%, non-condensing
REPO Port Meets NEC code 645-11 intent and UL requirements

Battery

Internal Battery Type Sealed, lead-acid; maintenance free
Battery Runtime See Battery Runtimes below
Battery Replacement Hot-swappable
Recharge Time <4 hours standard


Model Selection Guide

Model
Number

Power
Rating

Input
Connection

Output
Connection

Dimensions
HxWxD (in/cm)

Weight
(lb/kg)

Pre-configured Systems with Hardwire Input and Output

PW3S3K Includes:
(1) 3 slot enclosure
(1) power module
(1) battery module
(1) caster kit
3 KVA
expandable 
to 3kVA N+1 
Hardwired  Hardwired  19.5 x 17.0 x 25.5/ 
49.5 x 43.0 x 65.0
155.0/69.9
PW6S3K Includes:
(1) 6 slot enclosure
(1) power module
(2) battery module
(1) caster kit
3 KVA
expandable 
to 9kVA N+X 
Hardwired  Hardwired   33.3 x 17.0 x 25.5/
84.5 x 43.0 x 65.0
155.0/69.9
PW6S6K Includes:
(1) 6 slot enclosure
(2) power module
(4) battery module
(1) caster kit
6 KVA
expandable 
to 9kVA N+X 
Hardwired  Hardwired  33.3 x 17.0 x 25.5/
84.5 x 43.0 x 65.0
232.0/104.8
PW6S9K Includes:
(1) 6 slot enclosure
(3) power module
(6) battery module
(1) caster kit
6 KVA
expandable 
to 9kVA N+X 
Hardwired Hardwired  33.3 x 17.0 x 25.5/
84.5 x 43.0 x 65.0
346.0/156.7
PW9S9K Includes:
(1) 9 slot enclosure
(3) power module
(6) battery module
9 KVA
expandable 
to 18kVA N+X  
Hardwired  Hardwired  47.0 x 24.0 x 28.5/ 
119.5 x 61.0 x 72.5
389.0/176.7
PW12S9K Includes:
(1) 12 slot enclosure
(3) power module
(6) battery module
9 KVA
expandable 
to 18kVA N+X   
Hardwired Hardwired  60.7 x 24.0 x 28.5/ 
154.5 x 61.0 x 28.5
427.0/193.7
PW12S12K Includes:
(1) 12 slot enclosure
(4) power module
(8) battery module
12 KVA
expandable 
to 18kVA N+X 
Hardwired  Hardwired  60.7 x 24.0 x 28.5/ 
154.5 x 61.0 x 28.5
504.0/228.6
PW12S15K Includes:
(1) 12 slot enclosure
(5) power module
(10) battery module
15 KVA
expandable 
to 18kVA N+X 
Hardwired Hardwired  60.7 x 24.0 x 28.5/ 
154.5 x 61.0 x 28.5
581.0/263.5
PW12S18K Includes:
(1) 12 slot enclosure
(6) power module
(12) battery module
18 KVA
expandable 
to 18kVA N+X 
Hardwired  Hardwired  60.7 x 24.0 x 28.5/ 
154.5 x 61.0 x 28.5
658.0/298.4

Pre-configured Systems with Hardwire Input and Receptacles Output Options

PW6S3K-PD Includes:
(1) 6 slot enclosure
(1) power module
(2) battery module
(1) caster kit
3 KVA
expandable 
to 9kVA N+X
Hardwired  (2) L14-30R
(2) L6-30R
(12) 5-20R
33.3 x 17.0 x 25.5/ 
84.5 x 43.0 x 65.0
192.0/86.9
PW6S6K-PD Includes:
(1) 6 slot enclosure
(2) power module
(4) battery module
(1) caster kit
6 KVA
expandable 
to 9kVA N+X 
Hardwired  (2) L14-30R
(2) L6-30R
(12) 5-20R 
33.3 x 17.0 x 25.5/
84.5 x 43.0 x 65.0
269.0/121.8
PW6S9K-PD Includes:
(1) 6 slot enclosure
(3) power module
(6) battery module
(1) caster kit
9 KVA
expandable 
to 9kVA N+X 
Hardwired  (2) L14-30R
(2) L6-30R
(12) 5-20R
33.3 x 17.0 x 25.5/ 
84.5 x 43.0 x 65.0
346.0/160.7
PW9S9K-PD Includes:
(1) 9 slot enclosure
(3) power module
(6) battery module
9 KVA
expandable 
to 18kVA N+X 
Hardwired (2) L14-30R
(2) L6-30R
(12) 5-20R
47.0 x 24.0 x 28.5/ 
119.5 x 61.0 x 72.5
389.0/176.7
PW12S9K-PD Includes:
(1) 12 slot enclosure
(3) power module
(6) battery module
9 KVA
expandable 
to 18kVA N+X
Hardwired  (3) L14-30R
(3) L6-30R
(12) 5-20R
60.7 x 24.0 x 28.5/ 
154.5 x 61.0 x 28.5
427.0/193.7
PW12S12K-PD Includes:
(1) 12 slot enclosure
(4) power module
(8) battery module
12 KVA
expandable 
to 18kVA N+X 
Hardwired  (3) L14-30R
(3) L6-30R
(12) 5-20R 
60.7 x 24.0 x 28.5/ 
154.5 x 61.0 x 28.5
504.0/228.6
PW12S15K-PD Includes:
(1) 12 slot enclosure
(5) power module
(10) battery module
15 KVA
expandable 
to 18kVA N+X 
Hardwired  (3) L14-30R
(3) L6-30R
(12) 5-20R
60.7 x 24.0 x 28.5/ 
154.5 x 61.0 x 28.5
581.0/263.5
PW12S18K-PD Includes:
(1) 12 slot enclosure
(6) power module
(12) battery module
18 KVA
expandable 
to 18kVA N+X 
Hardwired (3) L14-30R
(3) L6-30R
(12) 5-20R
60.7 x 24.0 x 28.5/ 
154.5 x 61.0 x 28.5
658.0/298.4

Pre-configured Systems with Line Cord Input and Receptacles Output Options

PW3S3K-LPD Includes:
(1) 3 slot enclosure
(1) power module
(2) battery module
(1) caster kit
3 KVA
expandable 
to 9kVA N+X
L14-30P (1) L14-30R
(1) L6-30R
(4) 5-20R
19.5 x 17.0 x 25.5/ 
49.5 x 43.0 x 65.0
155.0/69.9
PW6S3K-LPD Includes:
(1) 6 slot enclosure
(1) power module
(2) battery module
(1) caster kit
3 KVA
expandable 
to 9kVA N+X 
14-50P (2) L14-30R
(2) L6-30R
(12) 5-20R 
33.3 x 17.0 x 25.5/
84.5 x 43.0 x 65.0
192.0/86.9
PW6S6K-LPD Includes:
(1) 6 slot enclosure
(2) power module
(4) battery module
(1) caster kit
6 KVA
expandable 
to 9kVA N+X 
14-50P (2) L14-30R
(2) L6-30R
(12) 5-20R
33.3 x 17.0 x 25.5/ 
84.5 x 43.0 x 65.0
269.0/121.8

UPS Cabinet Enclosures with Hardwire Input and Output Connections

PW9170+ 3 Slot  3 KVA Hardwired Hardwired 17.8 x 17.0 x 25.5/ 
45.0 x 43.0 x 65.0
66.0/30.0
PW9170+ 6 Slot  3 to 9kVA  Hardwired Hardwired 31.5 x 17.0 x 25.0/ 
80.0 x 43.0 x 65.0
103.0/47.0
PW9170+ 9 Slot  3 to 18kVA  Hardwired Hardwired 47.0 x 24.0 x 28.5/
119.5 x 61.0 x 72.5
158.0/72.0
PW9170+ 12 Slot  3 to 18kVA  Hardwired Hardwired 60.8 x 24.0 x 28.5/ 
154.0 x 61.0 x 72.5
196.0/89.0

Battery Cabinet Enclosures

6 Slot Battery Cabinet - DC Interconnect Option 
ASY-0525 Required 
- 17.8 x 17.0 x 25.5/ 
45.0 x 43.0 x 65.0
93.0/42.2
9 Slot Battery Cabinet DC Interconnect Option 
ASY-0525 Required 
- 47.0 x 24.0 x 28.5/ 
119.5 x 61.0 x 72.5
148.0/67.1
12 Slot Battery Cabinet DC Interconnect Option 
ASY-0525 Required 
- 60.8 x 24.0 x 28.5/ 
154.0 x 61.0 x 72.5
186.0/84.4

Available Modules

Split Phase Power Module 3 kVA/2.5kw - - 4.2 x 14.1 x 15.3/
10.6 x 35.8 x 38.9
17.0/7.7
Universal Power Module 3 kVA/2.5kw - - 4.2 x 14.1 x 15.3/
10.6 x 35.8 x 38.9
17.0/7.7
Battery Module - - - 4.2 x 7.0 x 14.8/
10.6 x 17.8 x 37.6
30.0/13.6
20 Amp Charger Module 3kVA  - - 4.2 x 14.1 x 15.3/ 
10.6 x 35.8 x 38.9
17.0/7.7

Notes: 50/60 Hz automatic frequency selection. Input/Output voltages 208-240 V or100/200,120/208, 127/220, 110/220 and 120/240 V. Split phase power Module offer both high and low output voltage. Universal Power Module offers only high output voltage. (3) and (6) slot enclosure dimensions include caster kit.

Battery Runtimes

Runtime Chart (full load / half load) Split-Phase Module ASY-0673
Load (VA) Number of Strings (2 battery modules per string)

  1 String 2 String 3 String 4 String  5 String 6 String 7 String 8 String
3kVA 6.5/16 16/40 27.5/67.5 40/98 53.5/132 67.5/167 83/204 98/242
6kVA    6.5/16 11/27.5 16/40 21.5/53.5 27.5/68 33.5/83 40/98
9kVA      65/16 9.5/23.5 13/31.5 16/40 20/49 23.5/58
12kVA        6.5/16 9/21.5 11/27.5 13.5/33.5 16/40
15kVA          6.5/16 8/20.5 10/25 12/30
18kVA            6.5/16 8/20 9.5/23.5
   
  9 String 10 String 11 String 12 String  13 String 14 String 15 String 16 String
3kVA 15/283 132.324 149/365 167/408 185/456 204/501 223/549 242/595
6kVA  46.5/15 53.5/132 60.5/149 575/167 75/85 83/204 90/223 98/242
9kVA  27.5/67.5 31.5/78 35.5/88 40/98 44/109 49/120 535/132 58/143
12kVA  19/46.5 21.5/53.5 24.5/60.5 27.5/68 30.5/75 33.5/83 37/90 40/98
15kVA  14/35 16/40 18.5/45 20.5/50.5 23/56 25/62 27.5/67.5 30/73.5
18kVA  11/27.5 18/44 14.5/35.5 16/40 18/44 20/49 21.5/53.5 23.5/58
                   
  17 String 18 String 19 String 20 String 21 String 22 String 23 String 24 String
3kVA 262/640 283/692 302/750 323/790 345/850 365/900 387/955 408/101.5
6kVA  106/262 115/285 123/302 132/324 140/345 149/365 157/388 167/408
9kVA  63/154 68/167 73/179 78/191 83/204 88/210 93/229 98/242
12kVA  43/106 46.5/115 50/123 53.5/132 57/140 60/149 64/157 68/167
15kVA  32.5/79.5 35/86 37.5*92 40/98 425/105 45/111 48/118 51/124
18kVA  25.5/63 27.5/68 29.5/73 31.5/78 33.5/83 35.5/88 38/93 40/98

 

Runtime Chart (full load / half load) Split-Phase Module ASY-0674
Load (VA) Number of Strings (2 battery modules per string)

  1 String 2 String 3 String 4 String  5 String 6 String 7 String 8 String
3kVA 8/24 24/59 43/95 58/140 80/175 95/215 119/240 135/290
6kVA    8/24 16/40 24/59 32/83 40/103 49/114 58/140
9kVA      8/24 13/35 18/46 24/59 29/63 35/86
12kVA        8/24 13/33 16/40 19.5/43.5 24/59
15kVA          8/24 11.5/31 14.5/31.5 18/49
18kVA            8/24 11/31.5 13/36
   
  9 String 10 String 11 String 12 String  13 String 14 String 15 String 16 String
3kVA 155/335 165/365 200/395 215/450 225/500 245/540 270/600 290/620
6kVA  69/156 83/175 90/190 103/205