Contact Us Toll Free
Buy
batteries on-line

Request Info
UPS Systems
Batteries
Emergency Lighting
Battery
Chargers
Battery Storage
Specials!
Service
Lease Info
| |
Power Factor Inc. will insure the Powerware PW9125-2000 P/N
05146001-6501 UPS is the right product for your application. Call 800-706-7009

Powerware 9125-2000 PW9125-2000 PW91252000 UPS



Low voltage
details
|
Electrical Input |
| Nominal
Voltage |
120 Vac
(user-selectable for 100, 110, 120, and 127 Vac
See Model Selection Guide |
|
Power Ratings |
700 - 2000VA;
See Model Selection Guide |
| Voltage
Range |
80 - 144V
(without using batteries) |
|
Input Power
Factor |
>.95, typical |
| Frequency |
50/60 Hz,
autosensing |
|
Frequency
Range |
45 - 65 Hz |
|
Electrical Output |
| On Utility
Voltage Regulation |
+/-3% of
nominal |
|
On Battery
Voltage Regulation |
+/-3% of
nominal |
| Efficiency |
89 - 92%,
depending on load |
|
Frequency
Regulation |
+/- 3 Hz
online; +/- 0.1 Hz on battery |
| Load Crest
Factor |
3 to 1
ratio |
|
Battery |
| Internal
Battery type |
Sealed,
lead-acid; maintenance free
700/1000VA: (2) 12V, 9 Ah
1250-2000VA: (4) 12V, 9 Ah |
|
EBM Battery
Type |
PW9125 24 EBM:
(8) 12V, 9 Ah
PW9125 48 EBM: (8) 12V, 9 Ah |
| On Battery
Runtime |
See
Battery Runtimes |
| Battery
Replacement |
Hot-swappable internal and external batteries |
|
Recharge Time |
<2 hrs. from
complete discharge to 80% capacity at nominal line conditions |
|
Start-On-Battery |
Allows
start of UPS without utility iinput |
|
Communications |
| Serial
Port |
RS-232
communications port standard |
|
Communications
Cable |
6-foot
communications cable included |
|
ConnectUPS-M
SNMP Module (Optional)2 |
SNMP card
adds direct control and monitoring capabilities in SNMP-based
networks |
|
RS-232
Multi-Port Module (Optional)2 |
Equipped with
(6) communications ports to provide serial communication to
multiple devices |
| USB Module
(Optional)2 |
Allows UPS
to communicate with Windows 98 computers via USB port;
factory-installed option only |
|
General |
| Topology |
True
online, double-conversion |
|
Diagnostics |
Full system
self-test on power up |
| UPS Bypass |
Automatic
on overload or UPS failure |
|
Dimensions and
Weights |
See
Model Selection Guide |
|
Environmental and Safety |
| Safety
Markings |
UL, CSA,
and NOM |
|
EMC Markings |
FCC Class B
and VCCI Class II |
| Surge
Suppression |
IEEE/ANSI
C62.41 Category B (formerly 587) |
|
Audible Noise |
<45 dBA (on
utility); <50 dBA (on battery) |
| Storage
Temperature |
0o
to 25o C (32o to 77o F) |
|
Relative
Humidity |
5 to 90%%,
non-condensing |
| REPO Port |
Meets NEC
code 645-II intent and UL requirements |
|
Network
Transient Protector |
In and out
jack for telephone/modem protection of 10Base-T network cable;
UL497A tested |
1Due
to continuing product improvement programs, specifications are
subject to change without notice.
2Optional in place of RS-232 serial port.
|
Model Selection Guide
Model
Number |
Part Number1 |
Power Out
(VA/Watt) |
Input/Output
Voltage (Vac)2 |
Frequency
(Hz)3 |
Input
Connection4 |
Output
Receptacles5 |
Dimensions
(HxWxD)6 |
Weight
(lb/kg)7 |
|
PW9125 700 |
05146012-5501 |
700/490 |
120 |
50/60 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x
19.4 in. |
34/15 |
|
PW9125 1000 |
05146002-5501 |
1000/700 |
120 |
50/60 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x
19.4 in. |
34/15 |
|
PW9125 1250 |
05146008-5501 |
1250/875 |
120 |
50/60 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x
19.4 in. |
50/23 |
|
PW9125 1500 |
05146005-5501 |
1500/1050 |
120 |
50/60 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x
19.4 in. |
50/23 |
|
PW9125 2000 |
05146001-5501 |
2000/1400 |
120 |
50/60 |
5-20P |
(6) 5-15R |
3.5 x 17.0 x
19.4 in. |
50/23 |
PW9125 2000
20R |
05146001-6506 |
2000/1400 |
120 |
50/60 |
5-20P |
(2) 5-20R
&
(4) 5-15R |
3.5 x 17.0 x
19.4 in. |
50/23 |
|
Optional Extended Battery Modules (EBMs) |
PW9125 24 EBM
700/1000VA models only |
05146502-5501 |
|
|
|
Standard
Connector |
|
3.5 x 17.0 x
19.4 in. |
65/29.5 |
PW9125 48 EBM
1250/2000VA models only |
05146074-5501 |
|
|
|
Standard
Connector |
|
3.5 x 17.0 x
19.4 in. |
65/29.5 |
1 For
UPS with factory-installed USB communications card, replace '-5501'
with '-5502'.
For UPS with Black Chasis Option, replace '-5501' with '-6501'.
2 Also user-selectable for 100, 110, and 127 Vac.
3 Automatic frequency selection.
4 6-ft. line cord.
5 Divided into 2 Load Segments (receptacle groups).
6 Unit fits in standard 19-inch racks. 1.2 inch front
panel
included in 19.4 inch dimension. Mounting kit is sold separately.
For tower configurations, the unit stands 17.0 inches high.
7 Add 8.5 lb. for shipping weight. |
Battery
Runtimes (in minutes)
|
700/1000 VA
Models |
|
Load |
Standard
Internal
Batteries |
1 EBM |
2 EBMs |
|
200VA/140W |
37 |
271 |
546 |
|
400VA/280W |
19 |
142 |
278 |
|
700VA/490W |
9 |
72 |
156 |
|
850VA/595W |
6 |
59 |
124 |
|
1000VA/700W |
5 |
48 |
104 |
1250-2000 VA Models |
|
Load |
Standard
Internal
Batteries |
1 EBM |
2 EBMs |
3 EBMs |
4 EBMs |
|
400VA/280W |
46 |
177 |
331 |
501 |
682 |
|
700VA/490W |
25 |
96 |
180 |
272 |
370 |
|
850VA/595W |
21 |
76 |
142 |
214 |
292 |
|
1000VA/700W |
16 |
61 |
115 |
174 |
237 |
|
1250VA/875W |
11 |
46 |
87 |
131 |
179 |
|
1500VA/1050W |
8 |
37 |
70 |
106 |
144 |
|
1800VA/1260W |
6 |
30 |
57 |
85 |
116 |
|
2000VA/1400W |
5 |
26 |
49 |
74 |
100 |
Battery Times are approximate and may vary with equipment,
configuration, disk access, battery age, temperature, etc.
|
|



High voltage
details
|
Electrical Input |
| Nominal
Voltage |
230 Vac
(user-selectable for 200, 220, 230, and 240 Vac
See Model Selection Guide |
|
Power Ratings |
700 - 2000VA;
See Model Selection Guide |
| Voltage
Range |
160 - 288V
(without using batteries) |
|
Input Power
Factor |
>.95, typical |
| Frequency |
50/60 Hz,
autosensing |
|
Frequency
Range |
45 - 65 Hz |
|
Electrical Output |
| On Utility
Voltage Regulation |
+/-3% of
nominal |
|
On Battery
Voltage Regulation |
+/-3% of
nominal |
| Efficiency |
89 - 92%,
depending on load |
|
Frequency
Regulation |
+/- 3 Hz
online; +/- 0.1 Hz on battery |
| Load Crest
Factor |
3 to 1
ratio |
|
Battery |
| Internal
Battery type |
Sealed,
lead-acid; maintenance free
700/1000VA: (2) 12V, 9 Ah
1250-2000VA: (4) 12V, 9 Ah |
|
EBM Battery
Type |
PW9125 24 EBM:
(8) 12V, 9 Ah
PW9125 48 EBM: (8) 12V, 9 Ah |
| On Battery
Runtime |
See
Battery Runtimes |
| Battery
Replacement |
Hot-swappable internal and external batteries |
|
Recharge Time |
<2 hrs. from
complete discharge to 80% capacity at nominal line conditions |
|
Start-On-Battery |
Allows
start of UPS without utility input |
|
Communications |
| Serial
Port |
RS-232
communications port standard |
|
Communications
Cable |
6-foot
communications cable included |
| ConnectUPS-M
SNMP Module (Optional)2 |
SNMP card
adds direct control and monitoring capabilities in SNMP-based
networks |
|
RS-232
Multi-Port Module (Optional)2 |
Equipped with
(6) communications ports to provide serial communication to
multiple devices |
| USB Module
(Optional)2 |
Allows UPS
to communicate with Windows 98 computers via USB port;
factory-installed option only |
|
General |
| Topology |
True
online, double-conversion |
|
Diagnostics |
Full system
self-test on power up |
| UPS Bypass |
Automatic
on overload or UPS failure |
|
Dimensions and
Weights |
See Model
Selection Guide |
|
Environmental and Safety |
| Safety
Markings |
UL, CSA,
CB, CE, S, D, N, FI, B, R |
|
EMC Markings |
FCC Class B
and VCCI Class II, CE, NZ, TAIWAN |
| Surge
Suppression |
IEEE/ANSI
C62.41 Category B (formerly 587) |
|
Audible Noise |
<45 dBA (on
utility); <50 dBA (on battery) |
| Storage
Temperature |
0o
to 25o C (32o to 77o F) |
|
Relative
Humidity |
5 to 90%%,
non-condensing |
| REPO Port |
Meets NEC
code 645-II intent and UL requirements |
|
Network
Transient Protector |
In and out
jack for telephone/modem protection of 10Base-T network cable;
UL497A tested |
1Due
to continuing product improvement programs, specifications are
subject to change without notice.
2Optional in place of RS-232 serial port.
|
Model Selection Guide
Model
Number |
Power Out
(VA/Watt) |
Input/Output
Voltage (Vac)2 |
Frequency
(Hz)3 |
Input
Connection4 |
Output
Receptacles5 |
Dimensions
(HxWxD)6 |
Weight
(lb/kg)7 |
|
120 Vac Models1 |
|
PW9125 700 |
700/490 |
120 |
50/60 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x
19.4 in.
89 x 432 x 494 mm |
34/15 |
|
PW9125 1000 |
1000/700 |
120 |
50/60 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x
19.4 in.
89 x 432 x 494 mm |
34/15 |
|
PW9125 1250 |
1250/875 |
120 |
50/60 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x
19.4 in.
89 x 432 x 494 mm |
50/23 |
|
PW9125 1500 |
1500/1050 |
120 |
50/60 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x
19.4 in.
89 x 432 x 494 mm |
50/23 |
|
PW9125 2000 |
2000/1400 |
120 |
50/60 |
5-20P |
(6) 5-15R |
3.5 x 17.0 x
19.4 in.
89 x 432 x 494 mm |
50/23 |
|
PW9125 2000 20 R |
2000/1400 |
120 |
50/60 |
5-20P |
(2) 5-20R &
(4) 5-15R |
3.5 x 17.0 x
19.4 in.
89 x 432 x 494 mm |
50/23 |
|
230 Vac Models7 |
|
PW9125 700i |
700/490 |
230 |
50/60 |
IEC-320C14 |
(6) IEC-320C13 |
3.5 x 17.0 x
19.4 in.
89 x 432 x 494 mm |
34/15 |
|
PW9125 1000i |
1000/700 |
230 |
50/60 |
IEC-320C14 |
(6) IEC-320C13 |
3.5 x 17.0 x
19.4 in.
89 x 432 x 494 mm |
34/15 |
|
PW9125 1250i |
1250/875 |
230 |
50/60 |
IEC-320C14 |
(6) IEC-320C13 |
3.5 x 17.0 x
19.4 in.
89 x 432 x 494 mm |
50/23 |
|
PW9125 1500i |
1500/1050 |
230 |
50/60 |
IEC-320C14 |
(6) IEC-320C13 |
3.5 x 17.0 x
19.4 in.
89 x 432 x 494 mm |
50/23 |
|
PW9125 2000i |
2000/1400 |
230 |
50/60 |
IEC-320C14 |
(6) IEC-320C13 |
3.5 x 17.0 x
19.4 in.
89 x 432 x 494 mm |
50/23 |
|
Optional Extended Battery Modules (EBMs) |
PW9125 24 EBM
700/1000VA models only |
|
|
|
Standard
Connector |
|
3.5 x 17.0 x
19.4 in.
89 x 432 x 494 mm |
65/29.5 |
PW9125 48 EBM
1250/2000VA models only |
|
|
|
Standard
Connector |
|
3.5 x 17.0 x
19.4 in.
89 x 432 x 494 mm |
65/29.5 |
1
Also user-selectable for 100, 110, and 127 Vac.
2 Automatic frequency selection.
3 120V models have 6-ft. attached line cord. 230V models
have 6-ft. detachable line cord.
4 Divided into 2 Load Segments (receptacle groups).
5 Unit fits in standard 19-inch racks. Mounting kit is
sold separately.
6 Add 8.5 lb. for shipping weight.
7 Also user-selectable for 220 and 240 Vac. |
Available Options
|
Order Number |
Description |
|
05146288-5501 |
X-Slot
ConnectUPS-M SNMP Module |
|
05146447-5501 |
X-Slot Multi-Port Module |
|
05141562-0021 |
4 post
rack-mount kit (fits 19-inch racks) |
|
05146726-5501 |
2 post rack-mount kit (fits 19-inch racks) |
|
05146871-5501 |
Seismic Kit,
Three Unit (for combination of up to 3 UPSs and/or EBMs) |
|
05146875-5501 |
Seismic Kit, Five Unit (for combination of up to 5 UPSs and/or EBMs) |
|
05146520-001 |
2000 VA Low
Voltage PowerPass Distribution Module |
|
05146519-001 |
700, 1000, 1250, 1500 VA Low Voltage PowerPass Distr. Module |
|
05146519-002 |
All 230V Models,
PowerPass Distribution Module |
Battery
Runtimes (in minutes)
|
700/1000 VA
Models |
|
Load |
Standard
Internal
Batteries |
1 EBM |
2 EBMs |
|
200VA/140W |
37 |
271 |
546 |
|
400VA/280W |
19 |
142 |
278 |
|
700VA/490W |
9 |
72 |
156 |
|
850VA/595W |
6 |
59 |
124 |
|
1000VA/700W |
5 |
48 |
104 |
1250-2000 VA Models |
|
Load |
Standard
Internal
Batteries |
1 EBM |
2 EBMs |
3 EBMs |
4 EBMs |
|
400VA/280W |
46 |
177 |
331 |
501 |
682 |
|
700VA/490W |
25 |
| | | |