Back Up Next Home Batteries  UPS Technology Emergency Lighting Battery Chargers Factory Links Contact Us Buy Batteries Online

Established 1996                              Call us 800-706-7009

.
Home GE Digital Energy LPC Powerware MGE Liebert MinuteMan ONEAC White Papers Remote Monitoring

.

 

Click here to Buy batteries online

Batteries
UPS Technology
Emergency Lighting
Battery Chargers
TVSS
9 Power Problems
Problems with Power
Factory Links
Contact Us

Powerware Manuals
PW3105
PW3110
PW5110
PW5115 Tower
PW5115 Rack
Evolution
Evolution S
PW5119
PW5125 Tower
PW5125 Rack/Tower
PW5130
PW5140
PW9104
PW9120
PW9125
EX Tower
EX Rack/Tower
PW9130 Tower
PW9130 Rack
PW9135
PW9140
PW9150
PW9155
PW9170
PW9170+
Prestige
Ferrups
BladeUPS
PW9305
PW9315
PW9330
PW9355
PW9390
Plus 18
Plus 36
IPK-0329

 

Powerware 5140

Contact us @ 800-706-7009 or click here for more information.                

Powerware 5140

Special features
  • Power Factor Corrected (PFC) design protects more equipment
  • 6U rack height conserves valuable rack space
  • Advanced Battery Management (ABM™) - doubles battery service life
  • Extended Battery Modules (EBMs) prolong run times
  • Load Segments (separate receptacle groups) enable scheduled shutdowns and maximize run times for critical devices.
Rating: 6000VA/6000Watts
Voltage: : 200-240 VAC
Frequency: 50 and 60 Hz
Configuration: 6U rack-mount for standard 19-inch racks
Topology: Line-interactive (with pure sine wave output)

 

 

Specification overview

  • Powerware Factor Corrected (PFC) design supports more equipment
  • Compact rack design (6U) conserves valuable rack space
  • Advanced Battery Management (ABM™) doubles battery service life
  • Buck and Boost voltage regulation provides pure sine wave output
  • Modular design eases scheduled shutdowns and maximizes runtime for critical devices
  • Hot-Swappable batteries and Manual Bypass Switch simplify service
Powerware 5140

Specification details

 

Electrical Input

 Voltage

200, 208, 220, 230 and 240 Vac user selectable; see Model Selection Guide for default settings

 Nominal Voltage Range

+/-20% of nominal voltage without using batteries

 Extended Voltage Range

160 - 288V without using batteries (set bia front panel)

 Frequency

50/60Hz, +/-3 Hz (+5/-3 Hz with extended voltage range)

 Connection

Hardwired

 Efficiency

96%

Electrical Output

 Power Out

 6000 VA/6000Watts

 Voltage

200, 208, 220, 230, 240

 Voltage Range (online)

 +/-10% of nominal voltage

 Voltage Range (on battery)

 +/-5% of nominal voltage

 Wave Form (on battery)

 Sine Wave

 Frequency

 Same as input (+/-0.5% during battery operation)

 Connections

 Receptacles or hardwired; see Model Selection Guide

 Maximum Current

29A at 208 Vac; 26A at 230 Vac

 Output Protection

Resettable circuit breakers

Battery

 Type Maintenance-free, sealed, valve-regulated lead-acid (VRLA), (28), 12V 5Ah
 Extended Batteries <Maximum of 2 Extended Battery Modules (EBMs)
 Backup Time See Battery Run Times Table
 Recharge Time <3 hours to 80% usable capacity
 Extended Battery Recharge Time <10 hours to 80% usable capacity

Communications

 Serial Ports

(2) Serial communication ports for use with power management software and installable option cards, including ConnectUPS SLC-EM SNMP Adapter and the Port Expander Card

 User LEDs

Normal Operation (green), On Battery (yellow), On Bypass (yellow), and Alarm (red)

 LCD

 Two-line LCD with three button control

 LCD Languages

 Danish, Dutch, English, French, German, Spanish, Italian, and Japanese

 Front Panel Buttons

 On, Off, and Alarm Silence/Self Test

 Connunication Cable

6-foot communication cable included

Environmental and safety

 Operating Temperature

 10oC to 40oC (25oC for optimal performance)

 Transit Temperature

-20oC to 55oC

 Storage Temperature

 0oC to 25oC

 Humidity (Operation)

20 to 80% (noncondensing)0

 Humidity (Non-operating)

5 to 95%

 Operating Altitude

0 to 10,000 feet (non-operating: 0 to 30,000 feet)

 Audible Noise

55 dBA at 1 meter

 Safety Markings

UL, CSA, NOM, Models PW5140 6000i and PW5140 6000 HW also CE and VDE

 Safety Certifications

UL1778; CSA22.2 No. 107.2, No.107.2, No. 950; CB Bulletin No.86AI; EN50091-1; EN60950; EMKO-TSE207/95; NOM-019-SCFI-1993

 EMC Markings

FCC-A, CISPR-A; VCCI

 Immunity

IEC 801-2, IEC 801-3, IEC 801-4, IEC 801-5

 Surge Suppression

Conforms to IEEE 587B and ANSI C62.41

 REPO Port

Meets NEC code 645-11 intent and UL requirements

 * Due to continuing product improvement programs, specifications subject to change without notice


Model Selection Guide

Model Number

Power Out (VA/Watt)

Input/Output Voltage (Vac)

Frequency (Hz)

Input Connection

Output Receptacles

Dimensions HxWxD (in/cm)

Weight (kg/lb)

PW5140 6000i 6000/6000 208/2302 50/603 Hardwired (12) IEC-320, C13 & (3) IEC-320, C194 10.5 x 17.25 x 24.3 in
26.7 x 43.8 x 61.7 cm
136/3006
PW5140 6000 6000/6000 208/2302 50/603 Hardwired (2) L6-30R & (2) IEC-3205 10.5 x 17.25 x 24.3 in
26.7 x 43.8 x 61.7 cm
136/3006
PW5140 6000 HW 6000/6000 208/2302 50/603 Hardwired Hardwired and (2) IEC-3205 10.5 x 17.25 x 24.3 in
26.7 x 43.8 x 61.7 cm
136/3006
PW5140 BATT       Custom Adapter   5.25 x 17.25 x 22.5 in
13.3 x 43.8 x 57.2 cm
81.6/180
PW5140 PDU7 250/250 120 60 Custom Adapter (2) 5-15R 1.98 x 19.28 x 9.90 in
5.03 x 48.97 x 25.15 cm
8.6/19

119-inch wide front panel with a 17.25-inch wide chassis; depth doesn not include front panel (0.5 inches). All models ship with rail mounting kit.
2208/230 Vac auto-sensing default. User selectable via LCD interface for 200, 208, 220, 230, and 240 Vac
3Automatic frequency synchronization.
4Divided into 5 Load Segments.
5Divided into 2 Load Segments; IEC-320 receptacles are used to connect optional PW5140 PDU.
6Shipping weight is 325 pounds (147 kg)
7Sidewall design occupies 0U of rack space.


Battery Run Times

Load (Watts) Standard
Batteries
One Additional
Extended Battery
Module
Two Additional
Extended Battery
Modules
1000

1 hr 2 mins

2 hrs 24 mins

3 hrs 56 mins

2000

28 mins

1 hr 6 mins

1 hr 47 mins

3000

18 mins

40 mins

1 hrs 6 mins

4000

12 mins

28 mins

47 mins

5000

8 mins

21 mins

36 mins

6000

6 mins

18mins

28mins

*This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature.etc.

 

 

Home Batteries  UPS Technology Emergency Lighting Battery Chargers Factory Links Contact Us Buy Batteries Online

Power Factor Inc.

2526 Manana Dr – Suite 102 – Dallas – Texas – 75220

800-706-7009

 Our Goal, NO DISSATISFIED CUSTOMERS!

Since 1995

While every precaution has been taken to ensure accuracy and completeness in this literature, Power Factor Inc. assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.