Contact Us Toll Free
Buy
batteries on-line

Request Info
UPS Systems
Batteries
Emergency Lighting
Battery
Chargers
Battery Storage
Specials!
Service
Lease Info
| |
Power Factor Inc. will insure the Powerware PW5125-1000 P/N
05146629-5501 UPS is the right product for your application.

Powerware 5125-1000 PW5125-1000 PW51251000 UPS
05146629-5501



|
Electrical Input |
1000-2200 VA |
2400-3000 VA |
|
Nominal
Voltage |
120, 208 and 230
Vac; See Model Selection Guide user-selectable volages |
120, 208, 230
and 240Vac; See Model Selection Guide user-selectable volages |
|
Input voltage
ranges for user-selectable voltages |
Low voltage:
77-152V; High voltage: 154-288V |
|
Operating
Frequency |
50/60Hz,
Auto-sensing |
|
Frequency
Range |
46-65Hz |
|
Electrical Output |
|
On Utility
Voltage Regulation |
-10% to +6% of
nominal |
|
On Battery
voltage Regulation |
±5% RMS |
|
Voltage Wave
Shape (on battery) |
Sine Wave |
|
Output
protection |
Short circuit
protection |
|
Battery |
|
Battery Type |
Sealed,
lead-acid; maintenance free |
|
Battery Run
time |
See Battery Run
Times Table |
|
Battery
Replacement |
Hot-swappable
internal batteries and external batteries modules |
|
Recharge Time |
<3 hours to 90%
usable capacity |
|
Start-On-Battery |
Allows start of
UPS without utility input |
|
General |
|
Diagnostics |
Full System
self-test on power up |
|
UPS Bypass |
No Bypass |
Internal Bypass |
|
Transfer Time |
2-4ms typical |
|
Dimensions
and weights |
See Model
Selection Guide |
|
Overload
(normal operation) |
110% overload,
shut down after 3 minutes. 150% overload, shut down 10 cycles |
110% overload
for 30 seconds short circuit protected |
|
Communications |
|
User
Interface |
Front Control
Panel |
|
Audible
Alarms |
For various UPS
alarm conditions, including: On Battery, Low Battery, Overload, UPS
fault |
|
Network
transient Protector |
UL 497 A,
In/out jacks RJ45 (high voltage models network protection) &
RJ11 (low voltage models modem protection) |
|
REPO Port |
Meets NEC code
645-11 intent and UL requirements |
|
X-Slot
Interface |
RS-232 Single
Serial Module (standard), Other options available: RS-232 Multi-Port
Module (6), SNMP/Web Module; USB Module; Relay Module |
|
Cable |
6-foot
communications cable included |
|
Power
Management Software |
Powerware
Software Suite CD-ROM (bundled with UPS) |
|
Environmental |
|
Safety
Certifications |
1UL; cUL; NOM;
C-Tick; CE mark |
|
EMC
Compliance |
FCC Part 15,
EN50091-2, Class A for 2.2KVA and RM; Class B for 1000 and 1500VA
tower models |
FCC Part 15,
EN50091-2, Class A |
|
Operating
Temperature |
0 to 40º C (32
to 104º F) |
|
Storage
Temperature |
-15 to 50º C (5
to 122º F) |
|
Relative
Humidity |
0% to 95%
non-condensing |
|
Lightning &
Surge Protection |
ANSI/IEEE C62.41
(IEEE 587), IEC61000-4-5 |
|
Surge energy
rating |
480 Joules |
|
Audible Noise |
Less than 40 dBA
typical |
|
Altitude |
3000m (10,000
ft) without derating |
|
Note:
Specifications are subject to change without notice due to
continuing product improvement programs. |
Model Selection Guide
|
Model
Number1 |
Power
Rating (VA/Watt) |
Input/
Output Voltage
(Vac)2 |
Input Connection |
Output Receptacles4 |
Dimensions HxWxD (in/mm) |
Weight (lb/kg) |
|
Tower
Models (North America) |
|
PW5125
1000 |
1000/700 |
120 |
5-15P,
6 ft line cord |
(6)5-15R |
9.45 x 6.38 x
15.79/
240 x 162 x 401 |
34.3/15.6 |
|
PW5125
1500 |
1440/1050 |
120 |
5-15P,
6 ft line cord |
(6)5-15R |
9.84 x 6.38 x
18.39/
250 x 162 x 467 |
50.7/23.0 |
PW5125
2200 |
1920/1600 |
120 |
5-20P,
6 ft line cord |
(6)5-15R,
(2)5-20R |
9.84 x 8.07 x
19.41/
250 x 205 x 493 |
68.3/31.0 |
PW5125
2200b |
2080/1600 |
208 |
IEC-320-15A,
inlet3 |
(9)IEC-320-10A |
9.84 x 8.07 x
19.41/
250 x 205 x 493 |
68.3/31.0 |
|
Tower
Models (International) |
|
PW5125
1000i |
1000/700 |
230 |
IEC-320-10A,
inlet3 |
(6)IEC-320-10A |
9.45 x 6.38 x
15.79/
240 x 162 x 401 |
34.3/15.6 |
|
PW5125
1500i |
1500/1050 |
230 |
IEC-320-10A,
inlet3 |
(6)IEC-320-10A |
9.84 x 6.38 x
18.39/
250 x 162 x 467 |
50.7/23.0 |
|
PW5125
2200i |
2200/1600 |
230 |
IEC-320-10A,
|
(9)IEC-320-10A |
9.84 x 8.07 x
19.41/
250 x 205 x 493 |
68.3/31.0 |
|
Two-in-One Form Factor Models5 (North America) |
|
PW5125
1000 RM |
1000/900 |
120 |
5-15P,
12 ft line cord |
(6)5-15R |
3.5 x 17.0 x
19.4/
89 x 432 x 494 |
34.0/15.0 |
|
PW5125
1500 RM |
1440/1050 |
120 |
5-15P,
12 ft line cord |
(6)5-15R |
3.5 x 17.0 x
19.4/
89 x 432 x 494 |
50.0/23.0 |
|
PW5125
2400 RM |
2400/2250 |
120 |
L5-30P,
12 ft line cord |
(1)L5-30R,
(6)5-15R |
3.5 x 19.0 x
24.5/
89 x 482.6 x 622.3 |
101.0/45.8 |
|
PW5125
3000 RM |
2880/2700 |
120 |
L5-30P,
12 ft line cord |
(1)L5-30R,
(6)5-15R |
3.5 x 19.0 x
24.5/
89 x 482.6 x 622.3 |
101.0/45.8 |
|
Two-in-One Form Factor Models5 (International) |
|
PW5125
1000i RM |
1000/700 |
230 |
IEC-320-10A,
inlet3 |
(6)IEC-320-10A |
3.5 x 17.0 x
19.4/
89 x 432 x 494 |
34.0/15.0 |
|
PW5125
1500i RM |
1500/1050 |
230 |
IEC-320-10A,
inlet3 |
(6)IEC-320-10A |
3.5 x 17.0 x
19.4/
89 x 432 x 494 |
50.0/23.0 |
|
PW5125
2400i RM |
2400/2250 |
230 |
L6-20P,
12 ft line cord |
(1)IEC-320-16A,
(9)IEC-320-10A |
3.5 x 19.0 x
24.5/
89 x 482.6 x 622.3 |
101.0/45.8 |
|
PW5125
3000g RM |
3000/2700 |
200-24 |
0 IEC-320-16A,
inlet3 |
(1)IEC-320-16A,
(9)IEC-320-10A |
3.5 x 19.0 x
24.5/
89 x 483 x 622 |
101.0/45.8 |
PW5125
3000i RM |
3000/2700 |
230 |
IEC-309-16A,
12 ft line cord |
(1)IEC-320-16A,
(9)IEC-320-10A |
3.5 x 19.0 x
24.5/
89 x 483 x 622 |
101.0/45.8 |
|
1. 50/60 automatic frequency selection.
2. 120V models 110V, 120V, 127V user-selectable. 230V models 220V,
230V, 240V user-selectable.208V models 208V, 220V, 230V, 240V
user-selectable
3. Includes(2) each IEC interconnect cables.
4. 1000-1500VA models divided into (2)Load Segments (receptacle
groups).2200-3000VA models divided into (3) Load Segments
(receptacle groups).
5. Unit fits in standard 19- inch racks. Mounting kits are sold
separately. |
Powerware 5125 Battery Run Time Chart (in minutes full load/half load)*
|
VA |
Standard Internal
Batteries |
1 EBM |
2 EBMs |
3 EBMs |
4 EBMs |
|
Tower Models |
|
1000 |
5/14 |
25/60 |
55/170 |
83/199 |
109/228 |
|
1500 |
6/17 |
33/79 |
63/146 |
92/174 |
120/201 |
|
2200 |
5/14 |
26/60 |
55/170 |
81/198 |
106/224 |
|
Two-in-One Form Factor |
|
1000 |
7/19 |
33/68 |
58/120 |
82/166 |
105/214 |
|
1500 |
5/13 |
23/57 |
49/161 |
73/172 |
96/205 |
|
2400 |
7/19 |
35/73 |
60/124 |
85/177 |
110/229 |
|
3000 |
5/15 |
25/61 |
49/103 |
69/146 |
96/205 |
*Up to 4 EBMs can
be connected to 1000-3000VA models. EBM run times include internal
batteries.
Run time chart provides typical information. Battery run times are
approximate and may vary with equipment, configuration, battery age,
temperature, etc.
|
|
Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS Powerware 5125-1000 PW5125-1000 PW51251000 UPS
PW5125 1000 PW5125 1500 PW5125 2200 PW5125 2200B
PW5125 1000 PW5125 1500 PW5125 2200 PW5125 2200B
PW5125 1000 PW5125 1500 PW5125 2200 PW5125 2200B
|