Powerware PW3110 300 500 700 UPS



|
Operation |
120V |
230V |
|
Nominal Input
Voltage |
120 Volts AC
(maximum 160 volts) |
230 Volts AC
(maximum 290 volts) |
|
Input Voltage
Range (for on-line operation) |
90-152 Volts |
176-272 Volts |
|
Operating
Frequency (on line) |
50/60
autosensing based on input frequency |
|
Nominal Output
Voltage |
120 VAC |
230 VAC |
|
Overload
Capacity |
120%±10% (3
minutes on line mode, 10 seconds on battery) |
|
Transfer Time |
6 ms typical |
|
On-Battery
Voltage |
120Vrms ±10% |
230Vrms ±10% |
|
Operating
Frequency |
50/60 Hz ±1Hz
autosensing |
|
Output Voltage
Waveform |
Regulated step
wave |
|
Output
Protection |
Electronically
limited |
|
Input
Protection |
Circuit
breaker |
|
Recharge Time
(to 95%capacity) |
8 hours
maximum |
|
Lightning &
Surge Protection |
ANSI/IEEE
C62.41 categories A&B, IEC801.4, 801.5 |
|
Surge Energy
Capacity |
450 Joules |
|
Efficiency |
>95%on line |
|
Safety
Certification |
UL1778,
Designed to meet UL497A, CAN/CSAÕC22.2 No.107.1 |
EN50091-1;CE
low voltage directive |
|
EMI Compliance |
FCC Class B |
EN55022,Class
B; CE EMC directive |
|
Communications |
DB-9,Contact
Closure |
|
Data Line
Protection |
fax/modem,network |
fax/modem |
|
Indicators |
On
line/Utility fail/Overload/Replace battery |
|
Audible Alarms |
Utility
fail/Overload/Replace battery |
|
Environmental |
|
Operating
Temperature |
0-40 °(32 to
104 °F) |
|
Storage
Temperature |
-15 to 50 °C
(5 to 122 °F) |
|
Relative
Humidity |
0-95%non-condensing |
|
Audible Noise
(normal operation) |
<40 dbA |
|
Altitude |
10,000
ft.(3,000m) |
| |
Model
Selection Guide
|
Voltage |
120V |
230V |
|
Model |
PW3110 300VA |
PW3110 550VA |
PW3110 700VA |
PW3110 300iVA |
PW3110 550iVA |
PW3110 700iVA |
|
Part Numbers |
05147642-5501 |
05147644-5501 |
05147646-5501 |
05147643-5501 |
05147645-5501 |
05147647-5501 |
|
Capacity (VA/Watt) |
300/180 |
550/330 |
700/420 |
300/180 |
550/330 |
700/420 |
Dimensions
(WxHxL)
in/mm |
3.9 x 2.3 x
15.5/
150 x 59 x 393 |
6.8 x 3.1 x
14.8/
172 x 79 x 376 |
3.9 x 2.3 x
15.5/
150 x 59 x 393 |
6.8 x 3.1 x
14.8/
172 x 79 x 376 |
Weight
(lb/kg) |
6.6/3.0 |
9.2/4.2 |
9.4/4.3 |
6.6/3.0 |
9.2/4.2 |
9.4/4.3 |
|
Input Connection |
NEMA 5-15P |
IEC-320 C14
(10amp) recessed socket* |
|
Output Receptacle Quantity & Type |
4 (UPS & Surge)
+ 2 (Surge only) NEMA 5-15R |
4 (UPS & Surge)
+2 (Surge only) C13 (10 amp) |
|
Typical Runtime: Minutes (Full Load) |
4 |
4 |
3 |
4 |
4 |
3 |
|
*230V models
include one jumper cord C13 and C14 type connectors. |
Powerware 3110 Run Times for Typical Applications in Minutes
|
Load (VA) |
100 |
150 |
200 |
250 |
300 |
350 |
400 |
450 |
500 |
550 |
600 |
650 |
700 |
|
300VA |
18 |
13 |
7 |
47 |
4 |
- |
- |
- |
- |
- |
- |
- |
- |
|
550VA |
30 |
22 |
18 |
14 |
11 |
10 |
8 |
6 |
4 |
4 |
- |
- |
- |
|
700VA |
39 |
22 |
17 |
16 |
14 |
13 |
9 |
7 |
6 |
5 |
5 |
3 |
3 |
Note: Due to continuing improvement programs specifications are subject