Contact Us Toll Free
Buy
batteries on-line

Request Info
UPS Systems
Batteries
Emergency Lighting
Battery
Chargers
Battery Storage
Specials!
Service
Lease Info
| |

Powerware Plus 36 UPS


 | LCD display
|
 | Fully automatic
bypass |
 | Extended battery
options |
 | Remote
monitoring capabilities |
 | System
Monitoring
- PowerVision® network software
- RS-232 port
- SNMP conversion |
|
 |
DC Expert.
Monitoring battery life is one of the most challenging aspects of UPS ownership.
DC Expert is a built-in battery monitoring system that helps administrators and
managers meet the challenges they face. The system provides accurate information
on run time and battery health, allowing organizations to avoid load losses due
to unexpected battery failure. While competitive battery monitoring systems
usually estimate run time with an +/- 20 percent fluctuation in accuracy, DC
Expert run time information is accurate within +/- 3 percent. Battery run time
is displayed on a large LCD panel located on the front of the system.
Outcall™ Paging
/Remote Notify. The Remote Notify system enhances proactive power
management, enabling the Powerware Plus to automatically call for help if power
or equipment problems occur. Remote Notify is an entry-level notification system
in which the Powerware Plus is connected to a phone line via an internal modem.
Remote Notify's outbound and inbound call capabilities save valuable time and
money by directly notifying a pager or personal computer. This alerts the
appropriate network manager or administrator and, in many cases, a problem can
be diagnosed and solved without visiting the site.
The Outcall Paging
feature allows the Powerware Plus to call as many as two telephone numbers
during an emergency. The number of outcalls per event is programmable and the
delay time between outcalls is also programmable.
Software. The
strong integration of software with Exide Electronics UPS hardware provides
additional power protection services for end users. PowerVision management
software is designed to monitor Exide Electronics UPS products, providing the
most sophisticated alarm management and notification tools available. FORESEER™'s
unique interface capability and performance analysis tools identify dangerous
trends, execute corrective action and prevent failures. All Powerware Plus
models above 18kVA have these management software capabilities.



24 - 36
kVA
 | Model 24 -
24kVA/16kW
200/115 - 220/127 VAC
|
 | Model 36 -
36 kVA/24kW
200/115 - 220/127 VAC |
|
|
|
Input |
|
Voltage Range |
See table below |
|
Frequency Range |
45-65 Hz |
|
Surge Protection |
Meets ANSI C62.41, Category A & B |
|
Power Factor |
0.95 Typical at full
load |
|
Output |
|
Voltage Regulation |
Better than +/- 2% |
|
Voltage THD |
Less
than 5% (100% nonlinear load); Less than 3% (100% linear load) |
|
Transient Response |
Less
than 5% for 100% load, step full recovery within 1/4 cycle |
|
Frequency Regulation |
(Free Run) +/- 0.1
Hz |
|
Frequency Sync
Range |
+/- 1.0 Hz |
|
Frequency Slew Rate |
1 Hz/sec. |
|
Load Crest Ratio |
3:1 |
|
Common Mode Noise Rejection |
>85 dB |
|
Battery |
|
Battery Type |
Sealed, maintenance-free lead acid |
|
Battery Voltage |
240
VDC |
|
Recharge time |
12x
discharge to 90% capacity |
|
Safety |
UL 1778 Listed
CUL CAN/CSA C22.2NO.107.1-M91 Listed
All Cabinets provide seismic mounting features |
|
Environmental and safety |
|
Audible Noise |
<60
dBA at 1 meter |
|
Ambient Operating Temperature |
0C
to 40C |
|
Ambient Storage Temperature |
-20C
to +60C |
|
Altitude |
5000 ft. (1500 m)
without derating |
|
Relative Humidity |
5-95% minimum non-condensing |
|
EMI Suppression |
Meet FCC Class A,
Subpart J of Part 15 |
|
Electrostatic
Discharge |
Withstands 25kV
without damage or disturbance to load |
*
Specifications subject to change without notice.
Model Selection
Guide
 | Model 24 -
24kVA/16kW
200/115 - 220/127 VAC
|
 | Model 36 - 36 kVA/24kW
200/115 - 220/127 VAC |
|
Nominal Voltage*
(Line-Line) |
Input
Voltage |
Model 24 |
Model
36 |
|
Max. |
Nominal |
Maximum
Rated
Current Per Phase |
Max. |
Nominal |
Maximum
Rated
Current Per Phase |
|
Input |
Output |
Range |
kVA |
KW |
Input |
Output |
kVA |
KW |
Input |
Output |
|
200 |
200 |
176-253 |
23.1 |
16 |
58A |
67A |
34.5 |
24 |
87A |
100A |
|
208 |
208 |
176-253 |
24.1 |
16 |
56A |
67A |
36 |
24 |
84A |
100A |
|
220 |
220 |
176-253 |
23.6 |
16 |
53A |
67A |
35.8 |
24 |
79A |
94A |
|
|
Model
24 HV |
Model
36 HV |
|
380 |
380 |
323-552 |
23.8 |
16 |
35A |
36A |
35.6 |
24 |
53A |
54A |
|
380 |
208 |
323-552 |
24.1 |
16 |
35A |
67A |
36 |
24 |
53A |
100A |
|
400 |
400 |
340-485 |
24.2 |
16 |
34A |
35A |
35.9 |
24 |
51A |
52A |
|
400 |
208 |
340-485 |
24.1 |
16 |
34A |
67A |
36 |
24 |
51A |
100A |
|
415 |
415 |
353-500 |
23.8 |
16 |
32A |
33A |
36 |
24 |
49A |
50A |
|
415 |
208 |
353-500 |
24.1 |
16 |
32A |
67A |
36 |
24 |
49A |
100A |
|
480 |
480 |
410-580 |
24.1 |
16 |
28A |
29A |
35.7 |
24 |
42A |
43A |
|
480 |
208 |
410-580 |
24.1 |
16 |
28A |
67A |
36 |
24 |
42A |
100A |
|
* Nominal UPS module input/voltage, i.e If unit is being used as a
voltage or frequency converter, the bypass must be disabled.
Input/Output voltage, phase and frequency must be equal for bypass
operation. Line to neutral voltage=line to line divided by 1.73 |
|
Battery Run Times
(in
minutes)
|
Output Watts |
1
Battery Cabinet |
2
Battery Cabinets |
3
Battery Cabinets |
|
8000 |
30 |
80 |
128 |
|
9000 |
25 |
72 |
110 |
|
10,000 |
22 |
65 |
98 |
|
11,000 |
20 |
57 |
88 |
|
12,000 |
18 |
50 |
78 |
|
13,000 |
15 |
45 |
70 |
|
14,000 |
14 |
40 |
62 |
|
15,000 |
13 |
35 |
56 |
|
16,000 |
12 |
30 |
50 |
|
17,000 |
11 |
27 |
47 |
|
18,000 |
10 |
24 |
43 |
|
19,000 |
9 |
22 |
40 |
|
20,000 |
8 |
20 |
37 |
|
21,000 |
7 |
18 |
35 |
|
22,000 |
6 |
17 |
33 |
|
23,000 |
5 |
16 |
31 |
|
24,000 |
5 |
15 |
30 |
|