Batteries UPS Technology Emergency Lighting Battery Chargers TVSS 9 Power Problems Olight Flashlights Problems with Power Factory Links Contact Us
Powerware Manuals Eaton 3S PW3105 PW3110 PW5110 PW5115 Tower PW5115 Rack Evolution Evolution S PW5119 PW5125 Tower PW5125 Rack/Tower PW5130 PW5140 PW9104 PW9120 PW9125 EX Tower EX Rack/Tower PW9130 Tower PW9130 Rack PW9135 PW9140 PW9150 PW9155 PW9170 PW9170+ Prestige Ferrups BladeUPS PW9305 PW9315 PW9330 PW9355 PW9390 Plus 18 Plus 36 Eaton 9E 3 Phase UPS IPK-0329
800-706-7009
A+ Rating with the Better Business Bureau
| |
Powerware Manuals • Eaton 3S • PW3105 • PW3110 • PW5110 • PW5115 Tower • PW5115 Rack • Evolution • Evolution S • PW5119 • PW5125 Tower • PW5125 Rack/Tower • PW5130 • PW5140 • PW9104 • PW9120 • PW9125 • EX Tower • EX Rack/Tower • PW9130 Tower • PW9130 Rack • PW9135 • PW9140 • PW9150 • PW9155 • PW9170 • PW9170+ • Prestige • Ferrups • BladeUPS • PW9305 • PW9315 • PW9330 • PW9355 • PW9390 • Plus 18 • Plus 36 • Eaton 9E 3 Phase UPS • IPK-0329

Eaton Powerware Plus 18 UPS
Contact us @ 800-706-7009 or click here for more information.


- LCD display
- Fully
automatic bypass
- Extended
battery options
- Remote
monitoring capabilities
- System
Monitoring
- PowerVision® network software
- RS-232 port
- SNMP conversion
|
 |
DC Expert.
Monitoring battery life is one of the most challenging aspects of UPS
ownership. DC Expert is a built-in battery monitoring system that helps
administrators and managers meet the challenges they face. The system
provides accurate information on run time and battery health, allowing
organizations to avoid load losses due to unexpected battery failure. While
competitive battery monitoring systems usually estimate run time with an +/-
20 percent fluctuation in accuracy, DC Expert run time information is
accurate within +/- 3 percent. Battery run time is displayed on a large LCD
panel located on the front of the system.
Outcall™ Paging
/Remote Notify. The Remote Notify system enhances proactive power
management, enabling the Powerware Plus to automatically call for help if
power or equipment problems occur. Remote Notify is an entry-level
notification system in which the Powerware Plus is connected to a phone line
via an internal modem. Remote Notify's outbound and inbound call
capabilities save valuable time and money by directly notifying a pager or
personal computer. This alerts the appropriate network manager or
administrator and, in many cases, a problem can be diagnosed and solved
without visiting the site.
The Outcall Paging
feature allows the Powerware Plus to call as many as two telephone numbers
during an emergency. The number of outcalls per event is programmable and
the delay time between outcalls is also programmable.
Software. The
strong integration of software with Exide Electronics UPS hardware provides
additional power protection services for end users. PowerVision management
software is designed to monitor Exide Electronics UPS products, providing
the most sophisticated alarm management and notification tools available.
FORESEER™'s unique interface capability and performance analysis
tools identify dangerous trends, execute corrective action and prevent
failures. All Powerware Plus models above 18kVA have these management
software capabilities. |
| |



12-18 kVA
- Model
12 - 12kVA/8kW
- Model
15 - 15 kVA/10kW
- Model
18 - 18kVA/12kW
|
|
|
Input |
|
Voltage Range |
See table below |
|
Frequency
Range |
45-65 Hz |
|
Surge
Protection |
Meets IEEE
587/ANSI C62.41, Category A & B |
|
Power
Factor |
0.95 Typical
at full load |
|
Output |
|
Voltage
Regulation |
Better than
+/- 3% |
|
Voltage THD |
Less than 5%
(100% nonlinear load); Less than 3% (100% linear load) |
|
Transient
Response |
Less than 5%
for 100% load, step full recovery within 1/4 cycle |
|
Frequency
Regulation |
(Free Run) +/-
0.1 Hz |
|
Frequency
Sync Range |
+/- 1.0 Hz |
|
Frequency
Slew Rate |
1 Hz/sec. |
|
Load Crest
Ratio |
3:1 |
|
Common Mode
Noise Rejection |
>100 dB |
|
Battery |
|
Battery Type |
Sealed,
maintenance-free lead acid |
|
Battery
Voltage |
240 VDC |
|
Recharge time |
12x discharge
to 90% capacity |
|
Safety |
UL 1778 Listed
CUL CAN/CSA C22.2NO.107.1-M91 Listed
EN 50091-1
All Cabinets provide seismic mounting features |
|
Environmental and safety |
|
Audible Noise |
<60 dBA at 1
meter |
|
Ambient
Operating Temperature |
0C to 40C |
|
Ambient
Storage Temperature |
-20C to +70C |
|
Altitude |
5000 ft. (1500
m) without derating |
|
Relative
Humidity |
5-95% minimum
non-condensing |
|
EMI
Suppression |
Meet FCC Class
A, Subpart J of Part 15 |
|
Electrostatic Discharge |
Withstands
25kV without damage or disturbance to load |
*
subject to change without notice.
Model
Selection Guide
|
Nominal Voltage*
(Line-Line) |
Input Voltage |
Model 12kVA/8kW |
Model 15kVA/10kW |
Model 18kVA/12kW |
|
Max. |
Maximum Rated
Current Per Phase |
Max. |
Maximum Rated
Current Per Phase |
Max. |
Maximum Rated
Current Per Phase |
|
Input |
Output |
Range |
kVA |
Input |
Output |
kVA |
Input |
Output |
kVA |
Input |
Output |
|
200 |
200 |
176-253 |
11.7 |
29A |
34A |
14.5 |
36A |
42A |
17.2 |
43A |
50A |
|
208 |
208 |
176-253 |
12.2 |
28A |
34A |
15 |
35A |
42A |
18 |
42A |
50A |
|
220 |
220 |
176-253 |
11.8 |
26A |
31A |
14.8 |
33A |
39A |
17.9 |
39A |
47A |
|
|
Model 12kVA/8kW HV |
Model 15kVA/10kW HV |
Model 15kVA/10kW HV |
|
380 |
380 |
367-391 |
12 |
15A |
18A |
15 |
19A |
23A |
18 |
23A |
27A |
|
400 |
400 |
388-412 |
11.9 |
14A |
17A |
15 |
18A |
22A |
17.9 |
22A |
26A |
|
415 |
415 |
403-427 |
12 |
14A |
17A |
15.6 |
18A |
22A |
18 |
21A |
25A |
|
480 |
480 |
467-494 |
11.6 |
12A |
14A |
15 |
15A |
18A |
18.3 |
18A |
22A |
|
480 |
208 |
467-494 |
11.9 |
12A |
33A |
15.1 |
15A |
42A |
18 |
18A |
50A |
|
* Nominal UPS module input/voltage, i.e If unit is being used
as a voltage or frequency converter, the bypass must be disabled.
Input/Output voltage, phase and frequency must be equal for bypass
operation. Line to neutral voltage=line to line divided by 1.73 |
|
Battery Run Times (in minutes)
|
Output Watts |
Standard Battery Configuration |
2 EBC2 Cabs |
1 EBC1 Cab** + 2 EBC2 Cabs*** |
3 EBC2 Cabs*** |
|
1000 |
146 |
198 |
250 |
301 |
|
2000 |
76 |
105 |
133 |
161 |
|
3000 |
50 |
70 |
89 |
109 |
|
4000 |
37 |
52 |
68 |
83 |
|
5000 |
28 |
40 |
52 |
65 |
|
6000 |
22 |
33 |
43 |
53 |
|
7000 |
18 |
27 |
36 |
44 |
|
8000 |
15 |
22 |
30 |
38 |
|
9000 |
12 |
19 |
26 |
33 |
|
10,000 |
10 |
16 |
22 |
29 |
|
11,000 |
8 |
14 |
20 |
25 |
|
12,000 |
7 |
12 |
17 |
22 |
*Estimated accuracy of
battery support times is +/-10%.
**EBC1 is one half-full battery cabinet.