Back Home Up Next  Batteries  UPS Technology Emergency Lighting Battery Chargers Factory Links Contact Us Buy Batteries Online

Established 1996                              Call us 800-706-7009

 

 

Click here to Buy batteries online

FE500VA
FE700VA
FE850VA
FE1.15kVA
FE1.4kVA
FE1.8kVA
FE2.1kVA
FE3.1kVA
FE4.3kVA
FE5.3kVA
FE7kVA
FE10kVA
FE12.5kVA
FE18kVA
Ferrups Manuals

Powerware Manuals
Eaton 3S
PW3105
PW3110
PW5110
Eaton 5S Series UPS
PW5115 Tower
PW5115 Rack
Evolution
Evolution S
PW5119
PW5125 Tower
PW5125 Rack/Tower
PW5130
Eaton 5P Tower
Eaton 5P Rack Mount UPS
Eaton 5PX
PW5140
PW9104
PW9120
PW9125
EX Tower
EX Rack/Tower
PW9130 Tower
PW9130 Rack
Eaton 9PX UPS
PW9135
PW9140
PW9150
PW9155
PW9170
PW9170+
Prestige
Ferrups
BladeUPS
PW9305
PW9315
PW9330
PW9355
PW9390
Plus 18
Plus 36
Eaton 9E 3 Phase UPS
IPK-0329
Eaton Paramount Enclosures

Power Factor Inc. will insure the Eaton Powerware FE3.1 FE3.1kVA Ferrups FH000JC3A0A0A0A FH010JC3A0A0A0A FH000AA0A0A0A0A FH010AA0A0A0A0A UPS is the right product for your application.

Contact us @ 800-706-7009 or click here for more information.

Model FE3.1 (3.1 kVA/2.2 kW)

General
Topology Ferroresonant
Part Number FH000AA0A0A0A0B
Color Beige with blue highlights
Rating (VA/Watts) 3100/2200
Dimensions (H x W x D, inches) 21.2 x 15.25 x 22.9
Weight (lbs) 256
Warranty Two-year factory warranty
Electrical Input
Connection Hardwired - example layout only Hardwired - see manual for terminal block layout
Nominal Voltage 120 VAC
Frequency 60 Hz
Input Power Factor 0.98
Electrical Output
Output Receptacles Hardwired - example layout only Hardwired - see manual for terminal block layout
On Utility Voltage Regulation ±3% for input voltages +15% to -20%
Overload Capacity 150% surge and 125% for 10 minutes on-line. 150% surge and 110% for 10 minutes on inverter.
Voltage Wave Shape (On Battery) Sine Wave
Transfer Time 0 ms
Battery
Half Load Runtime (in mins) 35
Full Load Runtime (in mins) 14
Communications
Communication Ports RS-232 serial port (DB-25),plus contact closures
Environmental & Standards
Operating Temperature 0° to 40°C
Lightning / Surge Protection 2000:1 spike attenuation using ANSI/IEEE C62.41 and C62.45 Category A and Category B tests.
Storage Temperature -20° to +60° C
Relative Humidity 5 to 95% without condensation
Note: Due to continuing product improvement programs, specifications are subject to change without notice.

Powerware ( Best Power ) Ferrups FE3.1Kva FE-3.1Kva 

Ferrups
Uninterruptible Power Systems

500VA to 18kVA
50Hz & 60Hz


Unmatched reliability in configurable power protection for computers and telecommunications equipment


Active Voltage Regulation
FERRUPS has unprecedented ability to work with all types of input sources and loads. Plus, its Active Voltage Regulation converts power from almost any AC source into computer-grade power.


Longer Runtime

FERRUPS provides regulated output voltage without drawing power from the batteries for input voltages as low as 38-percent below nominal (based on size of load). This keeps the batteries fully charged for unexpected blackouts.


Eliminates Harmonics

FERRUPS stops harmful harmonic currents generated by widely used switch-mode power supplies (SMPS) from entering a building’s wiring, where they could disrupt computer operations.


Computer Load Compatibility

FERRUPS can meet the demands of today’s computer loads, including power-factor corrected, switch-mode, and linear power supplies.


Enhanced Communications with Free Software

Every FERRUPS unit comes bundled with free CheckUPS® II Suite power management software and connecting cable. CheckUPS II helps users monitor, diagnose, and react more effectively to power-line events, and provides automatic, unattended shutdown when needed. The CD-ROM-based software supports most major operating systems. A BestLink™ SNMP/WEB Adapter can be connected for remote network operations.
 

Enhanced Diagnostics
FERRUPS initiates automatic startup and performs scheduled tests on the logic board, battery, inverter, and other critical systems.

Comprehensive Warranty Protection
FERRUPS is covered by our two-year limited warranty against factory or workmanship defects. We up the ante with our “Double Lifetime” limited warranty* that repairs or replaces your FERRUPS if damaged by lightning, and covers up to US$25,000 for damage to connected equipment. Call the factory for details on these limited warranties.

*U.S. and Canada only.

 

Ferrups
Uninterruptible Power Systems

500VA to 18kVA
60Hz


Unmatched reliability in configurable power protection for computers and telecommunications equipment


Spec details

 

 
Models 500VA 700VA 850VA 1.15kVA 1.4kVA 1.8kVA 2.1kVA 3.1kVA
Part Number FE500VA FE700VA FE850VA FE1.15kVA FE1.4kVA FE1.8kVA FE2.1kVA FE3.1kVA
Capacity (kVA/kW) .5/.35 .7/.5 .85/.6 1.15/.8 1.4/1 1.8/1.25 2.1/1.5 3.1/2.2
Dimensions
inches
mm
HxWxD

12 x 10 x 21.25
305 x 255 x 540

15.1 x 15.2 x 20.2
385 x 390 x 515


21.2 x 15.25 x 22.9
540 x 390 x 585

Weight
lbs
kg

62
28

79
36

85
39

132
60

154
70

183
83

196
89

256
116
Input Connection

6 ft cord w/NEMA 5-15P*

6 ft cord
w/NEMA 5-20P*
6 ft cord w/NEMA L5-30P*
Output Connection
quantity
type


4
NEMA 5-15R


4
NEMA 5-15R


4
NEMA 5-15R
Typical Runtime
full load
half load
(minutes)


9
25


14
35


11
28


18
48


14
37


11
30


9
25


14
35
Operation
Nominal Input Voltage 120/208/240
Input Voltage Range +15%, -20%
Input Power Factor 0.98
Nominal Output Voltage 120/208/240
Output Voltage Regulation ± 3% for input voltages of + 15% to -20%
Output Voltage Waveform Sine wave
Output Voltage THD 5% or less at rated kW load
Overload Capacity 150% surge and 125% for 10 minutes on-line,
150% surge and 110% for 10 minutes on inverter
Transfer Time 0 ms
Lightning, Surge & Noise Protection 2000:1 spike attenuation using ANSI/IEEE C62.41 Category A and Category B tests.
Common Mode - >120dB.  Normal Mode - >60dB
Efficiency 85 86 85 88 88 90 90 91
Safety Certification UL, CSA (cUL)
EMI Compliance FCC Class A
Testing Standards ANSI/IEEE C62.41 (1980); ANSI/IEEE C62.45 (1987); IEC 801-2, 801-4, 801-5
Communication RS-232 serial port (DB-25), plus contact closures
Environmental
Operating Temperature 0† to 40† C
Storage Temperature -20† C to +60† C (-20† C to +40† C if battery is not removed.)
Relative Humidity 0 to 95% without condensation
Storage Temperature -20† C to +60† C (-20† C to +40† C if battery is not removed.)
Audible Noise at 1m 41 41 47 49 49 51 51 51
Altitude 3,050 m (10,000 ft) maximum
All specifications subject to change without notice.
* 120V Standard Configuration

 

Models 4.3kVA   5.3kVA 7kVA 10kVA 12.5kVA 18kVA
Part Number FE4.3kVA FE5.3kVA FE7kVA FE10kVA FE12.5kVA FE18kVA
Capacity (kVA/kW) 4.3/3 5.3/3.7 7/5 10/7.5 12.5/10 18/15
Dimensions
inches
mm
HxWxD

29.5 x 15.5 x 25
750 x 395 x 635

36.5 x 19 x 32*
930 x 485 x 815
Weight
lbs
kg

359
163

505
229

604
274

875
397

1089
494

1362
618
Input Connection 120V/40A
208V/25A
240V/20A
120V/40A
208V/30A
240V/25A
120V/40A
208V/40A
240V/35A

208V/60A
240V/50A

208V/75A
240V/65A

208V=115A
240V=100A
Output Connection
 
Hardwired output is standard.  Contact Factory for receptacle options.
Typical Runtime
full load
half load
(minutes)


10
24


20
50


12
33


11
26


18
48


10
26
Operation
Nominal Input Voltage 208/240
Input Voltage Range +15%, -20%
Input Power Factor 0.98
Nominal Output Voltage 120/208/240
Output Voltage Regulation ± 3% for input voltages of + 15% to -20%
Output Voltage Waveform Sine wave
Output Voltage THD 5% or less at rated kW load
Overload Capacity 150% surge and 125% for 10 minutes on-line,
150% surge and 110% for 10 minutes on inverter
Transfer Time 0 ms
Lightning, Surge & Noise Protection 2000:1 spike attenuation using ANSI/IEEE C62.41 Category A and Category B tests.
Common Mode - >120dB.  Normal Mode - >60dB
Efficiency 90 90 90 90 91 92
Safety Certification UL, CSA (cUL)
EMI Compliance FCC Class A
Testing Standards ANSI/IEEE C62.41 (1980); ANSI/IEEE C62.45 (1987); IEC 801-2, 801-4, 801-5
Communication RS-232 serial port (DB-25), plus contact closures
Environmental
Operating Temperature 0° to 40° C
Storage Temperature -20° C to +60° C
Relative Humidity 0 to 95% without condensation
Audible Noise at 1m 50 51 52 55 56 57
Altitude 3,050 m (10,000 ft) maximum
All specifications subject to change without notice.
*Batteries in second cabinet.  Contact factory for weights and dimensions.

Eaton Powerware FE3.1 FE3.1kVA Ferrups FH000JC3A0A0A0A FH010JC3A0A0A0A FH000AA0A0A0A0A

Call for price

 Replacement batteries are available, call 800-706-7009 for details.

FE3.1KVA Ferrups

Power Factor Inc.

2526 Manana Suite 102 Dallas, Texas 75220

800-706-7009

Established 1996

While every precaution has been taken to ensure accuracy and completeness in this literature, Power Factor Inc. assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.