Eaton 9130 tower UPS. 2000 VA / 1800W, 120V, 5-20P input, (1)
L5-20R and (4) 5-20R output
| General |
| Topology |
Online, double-conversion |
| Catalog Number |
PW9130L2000T-XL |
| Color |
Black |
| Diagnostics |
Full system self-test |
| Efficiency |
>95% in high-efficiency mode; >86% in online mode |
| UPS Bypass |
Automatic bypass |
| Dimensions (H x W x D, inches) |
12.8 x 8.4 x 16.1 |
| Weight (lbs) |
76.1 |
| Warranty |
Two-year factory warranty |
| Rail Kit Included |
4-post rail kit included with all rackmount units |
Contents
(Ships with the following items) |
1 ready-to-go UPS
Software Suite CD
USB Cable
User Guide
Quick Start Instructions
4-post Rail Kit
Cord-Retention Brackets |
| Electrical Input |
| Connection |
5-20P |
| Input Cord |
6 ft line cord |
| Input Voltage Range |
90-138 Vac |
| Nominal Voltage |
120 VAC |
| Frequency |
50/60 Hz |
| Frequency Range |
45–65 Hz |
| Nominal Current |
16.6 A |
| Breaker Ratings |
20A |
| Electrical Output |
| Output Receptacles |
(4)
5-20R,
(1)
L5-20R |
| On Utility Voltage Regulation |
±3% of nominal |
| On Battery Voltage Regulation |
±3% of nominal |
| Voltage Wave Shape (On Battery) |
Sine wave |
| Power Factor |
0.9 |
| Frequency Regulation |
±3% Hz online |
| Load Crest Factor |
3 to 1 |
| Load Segments |
Two configurable, individually controlled
receptacles |
| Battery |
| Battery Type |
96 Vdc; (8) 12V, 9 Ah |
| Battery Type |
VRLA 12V/9 Ah (both internal and external) |
| Battery Runtime |
>3 minutes with internal batteries @ 100% load (0.9
PF) |
| Half Load Runtime (in mins) |
34 |
| Full Load Runtime (in mins) |
15 |
| Start On Battery |
Allows start of UPS without utility input |
| Communications |
| User Interface |
Graphical LCD with blue backlight and text in
English, French, German, Russian and Spanish |
| LEDs |
Four status-indicating LEDs |
| Communication Ports |
(1) USB, (1) RS-232 serial |
| Comunications Slot |
Optional communication slots (BD Slot) |
| Optional Communication Cards |
SNMP/Web card for direct control and monitoring in
SNMP-based networks, monitoring of UPS status and meters
through Web browser interface Relay card for integration
to industrial environment and building management
systems, remote shutdown for IBM AS/400 systems |
| Power Management Software |
Bundled software suite CD |
| Environmental &
Standards |
| Heat Dissipation (BTU) |
Line: 838, Bat: 1348 |
| Audible Noise |
<50 dB |
| Operating Temperature |
-20˚C (-4˚F) to +40˚C (104˚F) with batteries and
-25˚C (-13˚F) to +55˚C (131 ˚F) without batteries |
| Safety markings |
UL, CUL, VCCI |
| EMC Markings |
FCC Class A, EN55022 Class A |
| Storage Temperature |
5–90% non-condensing |
| Note: Due to continuing product
improvement programs, specifications are subject to
change without notice. |