Back Home Up Next  Batteries  UPS Technology Emergency Lighting Battery Chargers Factory Links Contact Us Buy Batteries Online

Division of Metroplex Battery Company - 800-372-4066         

Call us 800-706-7009 

 

 

Click here to Buy batteries online

PW9130L700R-XL2U
PW9130L1000R-XL2U
PW9130L1500R-XL2U
PW9130L2000R-XL2U
PW9130L2500R-XL2U
PW9130L3000R-XL2U
PW9130G1000R-XL2UEU
PW9130G1000R-XL2U
PW9130G2000R-XL2UEU
PW9130G2000R-XL2U
PW9130G2500R-XL2UEU
PW9130G2500R-XL2U
PW9130G3000R-XL2UEU
PW9130G3000R-XL2U
PW9130i1000R-XL2U
PW9130i1500R-XL2U
PW9130i2000R-XL2U
PW9130 Rack Manual

Powerware Manuals
Eaton 3S
PW3105
PW3110
PW5110
Eaton 5S Series UPS
PW5115 Tower
PW5115 Rack
Evolution
Evolution S
PW5119
PW5125 Tower
PW5125 Rack/Tower
PW5130
Eaton 5P Tower
Eaton 5P Rack Mount UPS
Eaton 5PX
PW5140
PW9104
PW9120
PW9125
EX Tower
EX Rack/Tower
PW9130 Tower
PW9130 Rack
Eaton 9PX UPS
PW9135
PW9140
PW9150
PW9155
PW9170
PW9170+
Prestige
Ferrups
BladeUPS
PW9305
PW9315
PW9330
PW9355
PW9390
Plus 18
Plus 36
Eaton 9E 3 Phase UPS
IPK-0329
Eaton Paramount Enclosures

Power Factor Inc. will insure the Eaton Powerware PW 9130 PW9130G3000R-XL2U UPS is the right product for your application.

Contact us @ 800-706-7009 or click here for more information.

PW9130 Powerware PW9130G3000R-XL2U Online Double Conversion Rackmount UPS

Eaton 9130 3000G RACK UPS Specifications

Eaton 9130 3000G RACK UPS Specifications

The Eaton 9130 Rackmount UPS delivers online power quality and scalable battery runtimes for rack servers, voice and data networks, storage systems and other IT equipment.

PW9130G3000R-XL2U

General
Topology Online, double-conversion
Configuration Rackmount
Color Black
Rating (VA/Watts) 3000/2700
Diagnostics Full system self-test
Efficiency >95% in high-efficiency mode; >86% in online mode
UPS Bypass Automatic bypass
Dimensions (H x W x D, inches) 3.4 x 17.2 x 23.6
Weight (lbs) 65
Warranty Two-year factory warranty
Rail Kit Included Included with all rackmount units
Remote Emergency Power off (REPO) Emergency shutdown control through the REPO port
Contents
(Ships with the following items)
1 ready-to-go UPS
Software Suite CD
USB Cable
User Guide
Quick Start Instructions
4-post Rail Kit
Electrical Input
Connection L6-20P L6-20P
Input Cord 6 ft. Detachable
Input Voltage Range 160-276 Vac
Nominal Voltage 208V
Frequency 50/60 Hz
Frequency Range 4565 Hz
Nominal Current 14.4 A
Breaker Ratings 16A
Generator Compatability Yes
Electrical Output
Output Receptacles L6-20R(1) L6-20R, L6-30R(1) L6-30R
On Utility Voltage Regulation 3% of nominal
On Battery Voltage Regulation 3% of nominal
Voltage Wave Shape (On Battery) Sine wave
Power Factor 0.9
Frequency Regulation 3% Hz online
Load Crest Factor 3 to 1
Battery
Maximum Number of Battery Packs 4
Battery Type 72 Vdc; (6) 12V, 9 Ah
Half Load Runtime (in mins) 13
Full Load Runtime (in mins) 5
Battery Replacement Hot-swappable internal and external batteries
Start On Battery Allows start of UPS without utility input
Recharge Time Internal batteries: 3 hours. 1 EBM: 9 hours; 2 EBM: 15 hours; 3 EBM: 21 hours; 4 EBM: 27 hours
Communications
User Interface Graphical LCD with blue backlight and text in English, French, German, Russian and Spanish
LEDs Four status-indicating LEDs
Communication Ports (1) USB, (1) RS-232 serial, Relay output (common alarm standard)
Comunications Slot Optional communication slots (BD Slot)
Optional Communication Cards SNMP/Web card for direct control and monitoring in SNMP-based networks, monitoring of UPS status and meters through Web browser interface Relay card for integration to industrial environment and building management systems, remote shutdown for IBM AS/400 systems
Power Management Software Bundled software suite CD
Environmental & Standards
RoHS Compliance Yes
Heat Dissipation (BTU) Line: 1257, Bat: 1755
Audible Noise <50 dB
Operating Temperature -20˚C (-4˚F) to +40˚C (104˚F) with batteries and -25˚C (-13˚F) to +55˚C (131 ˚F) without batteries
Safety markings UL, cUL, VCCI
EMC Markings FCC Class A, EN55022 Class A
Storage Temperature -20C (-4F) to +40C (104F) with batteries and -25C (-13F) to +55C (131 F) without batteries
Relative Humidity 590% non-condensing
Note: Due to continuing product improvement programs, specifications are subject to change without notice.

Go to top

Battery Backup Times (in minutes) at 0.7 Power Factor

Load (VA/Watts) Internal
Batteries
1 EBM 2 EBMs 3 EBMs 4 EBMs
3000/2100 6 25 45 68 96
2250/1575 8 34 70 96 130
1500/1050 14 62 92 156 211
750/525 34 130 212 355 442

Battery Backup Times (in minutes) at 0.9 Power Factor

Load (VA/Watts) Internal
Batteries
1 EBM 2 EBMs 3 EBMs 4 EBMs
3000/2700 4 19 34 53 69
2250/2025 5 29 53 79 103
1500/1350 9 45 84 122 165
750/675 27 102 175 263 344

Eaton Powerware PW 9130 PW9130G3000R-XL2U UPS

 

Power Factor Inc.

2526 Manana Suite 102 Dallas, Texas 75220

800-706-7009

Division of Metroplex Battery Company

While every precaution has been taken to ensure accuracy and completeness in this literature, Power Factor Inc. assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.