Power Factor Inc. will insure the Powerware PW9315 625-750Kva UPS
is the right product for your application. Call 800-706-7009




|
Input |
|
Voltage Range |
+10% to -15% |
|
Frequency Range |
+/-5% |
|
Surge Protection |
Meets ANSI C62.41, Category A & B, EN 50091-2 and EN 50082-2 |
|
Power Factor |
0.85 Typical at
full load |
|
Output |
|
Voltage Regulation |
Better than +/- 1% |
|
Voltage THD |
Less than 5% (100% nonlinear load); Less than 3% (100% linear load) |
|
Transient Response |
Less than 5% for 100% load, step full recovery within 1 cycle |
|
Frequency Regulation |
(Free Run) +/-
0.005 Hz |
|
Frequency Sync
Range |
+/- 0.5 Hz |
|
Frequency Slew Rate |
1 Hz/sec. |
|
Load Crest Ratio |
3:1 |
|
Safety (pending) |
| |
UL 1778 Listed
CUL CAN/CSA C22.2NO.107.1-M91 Listed EN 50091-1
All Cabinets provide seismic mounting features, selectable DC ground
fault detection capability |
|
Environmental |
|
Audible Noise |
<75 dBA at 1 meter |
|
Ambient Operating Temperature |
0C to 40C |
|
Ambient Storage Temperature |
-20C to 70C |
|
Altitude |
5000 ft. (1500 m)
at 40C without derating |
|
Relative Humidity |
5-95% non-condensing |
|
EMC |
Meet FCC Class A,
EN 50091-2 (CISPR 22, Class A, Restricted Access) |
|
Electrostatic
Discharge |
Withstands 25kV
without damage or disturbance to load |
*Specifications
subject to change without notice.
|
|
9315-750/750 |
9315-750/625 |
|
225kVA/180kW |
225kVA/180kW |
|
Input Voltage |
volts |
480 |
600 |
480 |
600 |
|
Output Voltage |
volts |
480 |
600 |
480 |
600 |
|
Input Voltage Range |
|
Minimum |
volts |
408 |
510 |
408 |
510 |
|
Maximum |
volts |
528 |
660 |
528 |
600 |
|
Input/Output Frequency |
Hz |
60 |
60 |
60 |
60 |
|
AC Input |
|
Nominal Amps |
amps |
913 |
730 |
761 |
609 |
|
Maximum Amps |
amps |
1141 |
913 |
951 |
761 |
|
Bypass Input |
|
|
Nominal Amps |
amps |
902 |
722 |
752 |
601 |
|
AC Ouput |
|
Nominal Amps |
amps |
902 |
722 |
752 |
601 |
|
10 minutes max |
amps |
1128 |
902 |
940 |
752 |
|
DC Link |
|
Nominal DC Voltage |
volts |
384 |
384 |
384 |
384 |
|
Float Voltage |
volts |
432 |
432 |
432 |
432 |
|
End of Discharge |
volts |
320 |
320 |
320 |
320 |
|
Nominal Amps |
amps |
1954 |
9554 |
1628 |
1628 |
|
Physical Attributes (w/o batt.) |
|
Single Module
RT Configurations |
|
Installed Weight |
lbs |
13,200 |
13,200 |
13,200 |
13,200 |
|
Installed Width |
inches |
149" |
149" |
149" |
149" |
|
Multimodule
Configurations |
|
Installed Weight |
lbs |
12,600 |
12,600 |
12,600 |
12,600 |
|
Installed Width |
inches |
126 5/8" |
126 5/8" |
126 5/8" |
126 5/8" |
|
System Efficiencies |
|
100% Load |
% |
94 |
94 |
94 |
94 |
|
75% Load |
% |
94 |
94 |
94 |
94 |
|
50% Load |
% |
93 |
93 |
93 |
93 |
|
Full Load Heat Dissipation |
|
BTU/Hr. (x1000) |
|
130.8 |
130.8 |
109.0 |
109.0 |
|
KCal/Hr.
(x1000) |
|
33.0 |
33.0 |
27.5 |
27.5 |
|
Inverter Efficiency (Full Load) |
% |
95 |
95 |
95 |
95 |
|
|