800-706-7009

 

Home • Up • 9315 100-160 KVA • 9315 200 - 300 KVA • 9315 30 - 80 KVA • 9315 400 - 500 KVA • 9315 625 - 750 KVA

 

 

Contact Us Toll Free

Buy batteries on-line

Request Info

UPS Systems

Universal Battery Valve Regulated Lead Acid Batteries Batteries

  Emergency Lighting

Battery chargers, rectifiers, dc power systems by SENS Battery Chargers

Click for more about the Battery Rack™ 20 with Tester (Grey) Battery Storage

Specials!

Service

Lease Info

 

Power Factor Inc. will insure the Powerware PW9315 400-500Kva UPS is the right product for your application. Call 800-706-7009

Powerware - Uninterruptible Power Systems

Powerware 9315

Technical Specification
 

400 - 500 kVA

 

bullet 9315-400/300 - 300kVA/240kW
bullet 9315-400/400 - 400kVA/320kW
bullet 9315-500/400 - 400kVA/320kW
bullet 9315-500/500 - 500kVA/400kW

 

Input

Voltage Range

See table below

Frequency Range

(60Hz) 57-64HZ

Surge Protection

Meets ANSI C62.41, Category A & B
EN 50091-2 and EN50082-2

Power Factor 0.95 Typical at full load

Output

Voltage Regulation

Better than +/- 1%

Voltage THD

Less than 5% (100% nonlinear load);
Less than 3% (100% linear load)

Transient Response

Less than 5% for 100% load, step full recovery within 1 cycle

Frequency Regulation (Free Run) +/- 0.005 Hz
Frequency Sync Range +/- 0.5 Hz
Frequency Slew Rate 1 Hz/sec.
Load Crest Ratio 3:1

Battery

Battery Type

Sealed, valve regulated lead acid

Recharge time

10-12x discharge to 95% capacity

Safety UL 1778 Listed
CUL CAN/CSA C22.2NO.107.1-M91 Listed
All Cabinets provide seismic mounting features selectable DC ground fault detection capability

Environmental and safety

Audible Noise

<72 dBA at 1 meter

Ambient Operating Temperature

0C to 40C

Ambient Storage Temperature

-20C to +70C

Altitude 5000 ft. (1500 m) without derating

Relative Humidity

5-95% non-condensing

EMI Suppression Meet FCC Class A, Subpart J of Part 15 and
EN 50091-2 (CIPR22,ClassA)
Electrostatic Discharge Withstands 25kV without damage or disturbance to load

* Specifications subject to change without notice.

 

-

9315-400/400 

9315-400/300

9315-500/500

 9315-500/400

 200kVA/160kW

 200kVA/160kW

 250kVA/200kW

  225kVA/180kW

Input  Range
Input Voltage  volts

 400

400

 480

 480

480

208

Output Voltage
Output Voltage  volts

 400

 400

 480

 480

208

208

Input Voltage Range

 Minimum

 volts

 340

 340

 408

 408

408

 177

 Maximum

 volts

 440

 440

 528

 528

 528

 229

Input /Output Frequency  Hz

50/60

50/60

60

 60

 60

 60

AC output (with input filter)

 Nominal Amps

 amps

 508

 381

 556

 445

445

1025

 Maximum Amps

 amps

 635

 476

 640

 560

560

1280

AC Output (without input filter)

 Nominal Amps

 amps

 598

 448

 654

 523

523

N/A

 Maximum Amps

 amps

 747

 560

 800

640 

640

N/A

Bypass Input

 Nominal Amps

 amps

 577

 433

 600

 480

480

1280

AC Output

 Nominal Amps

 amps

 577

 433

 600

 480

1110

1110

 10 Minutes Max.  amps

 721

 541

 750

 600

1388

 1388

DC Link

 Nominal DC Voltage

 volts

 420

 420 

 480

 480

 480

 480

 Float Voltage

 volts

 473

 473

 540

 540

 540

 540

 End of Discharge

 volts

 351

 351

 401

 401

 401

 401

 Maximum Amps

 amps

 914

 686

 1000

 800

 800

 800

Physical Attributes (with-out battery)

 Installed Weight

 lbs

 6100

 6100

 6100

 6100

 10,100

 14,100

 Installed Width

 inches

 74

 74

 74

 74

 123

 172

System efficiencies

 100% Load

 %

 92

 92

 92

 92

 91

 90

 75% Load

  %

 92

 92

 92

 92

 91

 90

 50% Load

  %

 91

 91

 91

 91

 90

 89

Full Load heat Dissipation

 BTU/Hr. (x1000)

 

95.6

 71.7

 95.6

  107.3

 107.3

119.0

 KCal/Hr. (x1000)

 

24.1

18.1

 30.2

 24.1

 27.1

30.0

Inverter Efficiency (full load)
-   %

 92.5

 92.5

 92.5

 92.5

 92.5

 92.5


Battery Run Times
(in minutes)

 

50 Hz Applications

  Installed 9315-400
Battery
Type
Qty Cabinet
Series
Weight
(lbs.)
Width1
(inches)
300kVA
240kW
400kVA
320kW
J14 1 685 1,785 27 N/A N/A
J17 1 685 2,250 27 N/A N/A
J127 1 1085 2,865 43 N/A N/A
J31 1 1085 3,165 43 N/A N/A
J37 1 1085 3,395 43 N/A N/A
J47 1 1085 4,300 43 N/A N/A
J14 2 685 3,570 54 N/A N/A
J17 2 685 4,500 54 N/A N/A
J27 2 1085 5,730 86 N/A N/A
J31 2 1085 6,330 86 N/A N/A
J37 2 1085 6,790 86 5 N/A
J27 3 1085 8,595 129 N/A N/A
J31 3 1085 9,495 129 9 9
J37 3 1085 10,185 129 12 7
J47 3 1085 12,900 129 18 11
J27 4 1085 11,460 172 12 7
J31 4 1085 12,660 172 15 9
J37 4 1085 13,580 172 19 12
J47 4 1085 17,200 172 29 18

Nominal DC Link Voltage

420 420
 Number Of Cells per Cabinet

 210

210

1 All battery cabinets are 73.5 inches high and 31.5 inches deep. 

60 Hz Applications

  Installed 9315-500
Battery
Type
Qty Cabinet
Series
Weight
(lbs.)
Width1
(inches)
400kVA
320kW
500kVA
400kW
J102 1 1085 2,545 43 N/A N/A
J14 1 685 1,915 27 N/A N/A
J17 1 685 2,450 27 N/A N/A
J27 1 1085 3,150 43 N/A N/A
J31 1 1085 3,495 43 N/A N/A
J37 1 1085 3,765 43 N/A N/A
J47 1 1085 4,800 43 N/A N/A
J14 2 685 3,830 54 N/A N/A
J17 2 685 4,900 54 N/A N/A
J27 2 1085 6,330 86 N/A N/A
J37 2 1085 6,300 86 N/A N/A
J31 2 1085 6,990 186 N/A N/A
J37 2 1085 7,530 86 N/A N/A
J47 2 1085 9,600 86 5 N/A
J27 3 1085 9,450 129 N/A N/A
J31 3 1085 10,485 129 7 N/A
J37 3 1085 11,295 129 9 5
J47 3 1085 14,400 129 14 9
J27 4 1085 12,600 172 9 5
J31 4 1085<