Input |
|
Voltage Range |
See table below |
|
Frequency Range |
(60Hz) 57-64HZ
(50Hz) 47-53Hz |
|
Surge Protection |
Meets ANSI C62.41, Category A & B
EN 50091-2 and EN50082-2 |
|
Power Factor |
0.95 Typical at
full load |
|
Output |
|
Voltage Regulation |
Better than +/- 1% |
|
Voltage THD |
Less than 5% (100% nonlinear load); Less than 3% (100% linear load) |
|
Transient Response |
Less than 5% for 100% load, step full recovery within 1 cycle |
|
Frequency Regulation |
(Free Run) +/-
0.005 Hz |
|
Frequency
Sync Range |
+/- 0.5 Hz |
|
Frequency Slew Rate |
1 Hz/sec. |
|
Load Crest
Ratio |
3:1 |
|
Battery |
|
Battery Type |
Sealed, maintenance-free lead acid |
|
Recharge time |
10-12x discharge to 95% capacity |
|
Safety |
UL 1778 Listed
CUL CAN/CSA C22.2NO.107.1-M91 Listed
All Cabinets provide seismic mounting features selectiable DC ground
fault detection capability |
|
Environmental and safety |
|
Audible Noise |
<65 dBA at 1 meter |
|
Ambient Operating Temperature |
0C to 40C |
|
Ambient Storage Temperature |
-20C to +60C |
|
Altitude |
5000 ft. (1500
m) without derating |
|
Relative Humidity |
5-95% non-condensing |
|
EMI Suppression |
Meet FCC Class
A, Subpart J of Part 15 and
EN 50091 (CIPR22,ClassA) |
|
Electrostatic
Discharge |
Withstands 25kV
without damage or disturbance to load |