| Description |
APC Smart-UPS,
5000VA/3750W, Rack Mount 5U, Input 208V/ Output 208V |
 |
| General Features |
Automatic Voltage
Regulation (AVR) , Hot Swap Batteries , Intelligent Battery Management ,
Overload Indicator , Rack Mount , Replace Batt Indicator , SmartSlot ,
Software , User Replaceable batteries |
 |
| Includes |
CD with software ,
Rack Mounting support rails , Smart UPS signalling RS-232 cable , User
Manual |
 |
 |
| |
Technical Specifications |
 |
|
|
Output |
 |
| Rated Power |
5,000 VA |
 |
| Output power
capacity |
3,750 Watts |
 |
| Nominal output
voltage |
208 V |
 |
| Output Voltage
Note |
Also provides up
to 400VA of 120V with (2) NEMA 5-15 receptacles |
 |
| Output Connections |
|
(2)NEMA 5-15R |
|
|
(2)NEMA L6-20R |
|
|
(1)NEMA L6-30R |
|
|
 |
| Optional AC
Connection |
optional
AC Connections. |
 |
| Waveform type |
Sinewave |
 |
 |
|
Input |
 |
| Nominal input
voltage |
208 V |
 |
| Input frequency |
50/60 Hz +/- 5 Hz
(auto sensing) |
 |
| Input Connection
Type |
|
NEMA L6-30P (30A
Twist-Lock) |
|
|
 |
| Cord Length |
6 feet |
 |
Input voltage
range
for main operations |
157 - 255 V |
 |
| Input voltage
adjustable range for main operations |
151 - 268 V |
 |
 |
|
Batteries |
 |
Typical backup
time
at half load |
17.7 minutes |
 |
| Battery type |
Maintenance-free
sealed Lead-Acid battery with suspended electrolyte : leakproof |
 |
| Typical recharge
time |
3 hour(s) |
 |
| Replacement
battery cartridge |
(2)
RBC12 |
 |
 |
|
Communications & Management |
 |
| Interface port |
DB-9 RS-232, RJ-45
10 Base-T ethernet for web/ SNM |
 |
| Smart Slot
Interface Quantity |
1 |
 |
| Management
software included |
PowerChute Smart-UPS Bundle |
 |
| Optional Software |
other
Software options . |
 |
| Control panel |
LED status display
with load and battery bar-graphs and On Line : On Battery : Replace Battery
: and Overload Indicators |
 |
| Audible alarm |
Alarm when on
battery : distinctive low battery alarm : configurable delays |
 |
| Emergency Power
Off (EPO) |
Optional |
 |
| Optional
Management Device |
optional
Management Devices. |
 |
 |
|
Surge Protection and Filtering |
 |
| Surge energy
rating |
480 Joules |
 |
| Filtering |
Full time
multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping
response time : meets UL 1449 |
 |
 |
|
Physical |
 |
| Maximum height
dimensions |
8.75 inches (
22.23 cm) |
 |
| Maximum width
dimensions |
19.00 inches (
48.26 cm) |
 |
| Maximum depth
dimensions |
25.00 inches (
63.50 cm) |
 |
| Rack Height |
5 U |
 |
| Net weight |
225.00 lbs (
102.27 kg) |
 |
| Shipping weight |
245.00 lbs (
111.36 kg) |
 |
| Shipping Height |
0.00 inches (
0.00 cm) |
 |
| Shipping Width |
0.00 inches (
0.00 cm) |
 |
| Shipping Depth |
0.00 inches (
0.00 cm) |
| Color |
Beige |
 |
 |
|
Environmental |
 |
| Operating
Temperature |
0 - 40 °C (32 -
104°F) |
 |
| Operating Relative
Humidity |
0 - 95% |
 |
| Operating
Elevation |
0-10000 feet
(0-3000 m) |
 |
| Storage
Temperature |
-15 - 45 °C (5 -
113°F) |
 |
| Storage Relative
Humidity |
0 - 95% |
 |
| Storage Elevation |
0-50000 feet
(0-15000 m) |
 |
| Audible noise at 1
meter from surface of unit |
53 dBA |
 |
| Online thermal
dissipation |
430 BTU/hr |
 |
 |
|
Conformance |
|
 |
| Approvals |
CSA, FCC Part 15
Class A, UL 1778 |
 |
| Standard warranty |
2 years repair or
replace , optional on-site warranties available , optional extended
warranties available |
 |
| Equipment
protection policy |
Lifetime : $25000 |