|
SECTION 5-9
EMERGENCY LIGHTING
5-9.1 General.
5-9.1.1 Emergency lighting facilities
for means of egress shall be provided in accordance with this section for
every building or structure where required in Chapters 8 through 30. For the
purposes of this requirement, exit access shall include only designated
stairs, aisles, corridors, ramps, escalators, and passageways leading to an
exit.
5-9.1.2 Where maintenance of
illumination depends upon changing from one energy source to another, there
shall be no appreciable interruption of illumination during the changeover.
5-9.2 Performance of System.
5-9.2.1* Emergency illumination shall be
provided for a period of 1-1/2 hours in the event of failure of normal
lighting. Emergency lighting facilities shall be arranged to provide initial
illumination that is no less than an average of 1 footcandle (10 lx) and a
minimum at any point of .1 footcandle (1 lx) measured along the path of
egress at floor level. Illumination levels may decline to .6 footcandle (6
lx) average and a minimum at any point of .06 footcandle (.6 lx) at the end
of the emergency illumination lighting time duration. A maximum to minimum
illumination uniformity ratio of 40 to 1 shall not be exceeded.
5-9.2.2* The emergency lighting
system shall be so arranged as to provide the required illumination
automatically in the event of any interruption of normal lighting, such as
any failure of public utility or other outside electrical power supply,
opening of a circuit breaker or fuse, or any manual act(s), including
accidental opening of a switch controlling normal lighting facilities.
5-9.2.4 Battery operated emergency
lights shall use only reliable types of rechargeable batteries provided with
suitable facilities for maintaining them in properly charged condition.
Batteries used in such lights or units shall be approved for their intended
use and shall comply with NFPA 70, National Electrical Code.®
5-9.2.5 The emergency lighting system
shall be either continuously in operation or capable of repeated automatic
operation without manual intervention.
5-9.3 Testing and Maintenance (See
Section 31-1) 31-1.3.1 Whenever or wherever any device, equipment, [or]
system...is required for compliance with the provisions of this Code, such
device, equipment, [or] system...shall thereafter be permanently maintained
unless the Code exempts such maintenance.
31-1.3.4 Any equipment requiring test
or periodic operation to assure its maintenance shall be tested or operated
as specified elsewhere in this Code or as directed by the authority having
jurisdiction.
31-1.3.5 Systems shall be under the
supervision of a responsible person who shall ensure that proper tests are
made at specified intervals and have general charge of all alterations and
additions.
31-1.3.7 Periodic Testing of
Emergency Lighting Equipment.
A functional test shall be conducted on every required emergency lighting
system at 30-day intervals for a minimum of 30 seconds. An annual test shall
be conducted for the 1-1/2 hour duration. Equipment shall be fully
operational for the duration of the test. Written records of testing shall
be kept by the owner for inspection by the authority having jurisdiction.
|
SECTION 5-10
MARKING OF MEANS OF EGRESS
5-10.1 General
5-10.1.2* Exits shall be marked by an
approved sign readily visible from any direction of exit access.
Exception: Main exterior exit doors that obviously and clearly are
identifiable as exits.
5-10.1.4 Access to exits shall be
marked by approved readily visible signs in all cases where the exit or way
to reach it is not readily apparent to the occupants. Sign placement shall
be such that no point in the exit access is more than 100 ft from the
nearest visible sign.
Exception: Signs in existing buildings need not meet the 100-ft distance
requirement.
5-10.1.5* Where floor proximity exit
signs are specifically required in Chapters 8 through 30, exit signs shall
be placed near the floor level in addition to those signs required for doors
or corridors by 5-10.1.2 and 5-10.1.3. These signs shall be sized and
illuminated in accordance with he requirements of 5-10.2 and 5-10.3. The
bottom of the sign shall be not less than 6 in. nor more than 8 in. above
the floor. For exit doors, the sign shall be mounted on the door or adjacent
to the door with the closest edge of the sign within 4 in. of the door
frame.
5-10.2* Size of Signs. Every sign
required by Section 5-10 shall have the word "EXIT" or other appropriate
wording in plainly legible letters not less than 6 in. (15.2 cm) high with
the principal strokes of letters not less than 3/4 in. (1.9 cm) wide. The
word "EXIT" shall have letters of a width not less than 2 in. (5 cm) except
the letter "I" and the minimum spacing between letters shall be not less
than 3/8 in. (1 cm). Signs larger than the minimum established in this
paragraph shall have letter widths, strokes, and spacing in proportion to
their height.
5-10.3 Illumination of Signs.
5-10.3.1* Every sign required by 5-10.1.2 or 5-10.3 shall be suitably
illuminated by a reliable light source. Externally and internally
illuminated signs shall be visible in both the normal and emergency lighting
mode.
5-10.3.2* Externally illuminated
signs shall be illuminated by not less than 5 footcandles (54lx) and shall
employ a contrast ratio of not less than 0.5.
5-10.3.3* The visibility of an
internally illuminated sign shall be the equivalent of an externally
illuminated sign that complies with 5-10.3.2.
Exception No. 1: Approved Existing Signs
Exception No. 2*: Approved self-luminous or electroluminescent signs that
provide evenly illuminated letters shall have a minimum luminance of 0.06
footlamberts as measured by a color-corrected photometer.
5-10.3.4 Every sign required by
5-10.1.4 shall provide evenly illuminated letters having a minimum luminance
of 0.06 footlamberts
Exception: Signs complying with the requirements of 5-10.3.3 are
acceptable.
|
Excerpted from
Life Safety Code 1994 (pp. 47-49, 226)
|
|