Contact Us Toll Free
Buy
batteries on-line

Request Info
UPS Systems
Batteries
Emergency Lighting
Battery
Chargers
Battery Storage
Specials!
Service
Lease Info
| |
|
CRITICAL AREA LIGHTING & EQUIPMENT
|
| |
|
|
1 |
An input high isolation
ferroresonant transformer provides power to a solid state rectifier, which
in turn, creates a regulated DC supply. This supply provides the power
requirements for the continuously running inverter. |
|
2 |
An input high isolation ferroresonant
transformer provides power to a solid state rectifier/charger, which in
turn, creates a regulated DC supply. This supply charges the battery |
|
3
|
A sealed maintenance free
battery is provided to maintain power to the inverter during a mains
failure. The battery is fitted with a suitably rated fuse to provide
overload and short circuit protection. |
|
4
|
A ferroresonant
transistorized static inverter transforms the DC voltage coming from either
the rectifier or the battery into regulated AC voltage to supply the
critical load. |
|
5
|
An electro/mechanical
automatic bypass switch connects the load normally to the inverter. In the
case of inverter failure or voluntary shutdown, the load is connected to the
utility. |
| |
High Efficiency
Uninterruptable Power Supply
|
| |
Ferroresonant technology
reduces circuit complexity which in turn, doubles the factory warranty. The
inverter utilizes internal transistor redundancy which will allow up to 20%
of the power switching transistors to fail and still provide full load
output power. This combination achieves a reliability record envied within
the industry. Units are floor-mounted, force cooled UPS systems, with front
access for servicing. Cabinets contain air filters and knockouts for
interwiring with BX, Romex, or Conduit. The internal module consists of a
battery charger, AC-DC converter, DC-AC inverter, and batteries. Above
1.5kVA, a separate battery cabinet is supplied. |
|
UPS
Series
|
S
Battery Type
(S ~ Sealed)
|
120
Input AC
Line Voltage
|
120
Output AC
Voltage
|
90
Battery Run Time
|
-CFA
Options
|
Mechanical Specifications
|
| Model Number |
kVA
Rating
|
Max Util
Input
Current
|
System
Efficiency
%
|
Heat
Loss
BTU's
|
Inverter Cabinet Dimension
|
Inverter
Weight
lbs.
|
|
(A)
Width
Inches
|
(B)
Height
Inches
|
(C)
Depth
Inches
|
| UPSS-1000-120-120-90 |
1
|
17
|
75
|
900
|
42
|
50
|
12
|
675
|
| UPSS-1500-120-120-90 |
1.5
|
25
|
75
|
1300
|
42
|
62
|
12
|
950
|
| UPSS-3000-120-120-90 |
3
|
50
|
75
|
2700
|
42
|
62
|
19
|
775
|
| UPSS-4500-120-120-90 |
4.5
|
75
|
75
|
4000
|
42
|
70
|
19
|
885
|
| UPSS-6000-120-120-90 |
6
|
100
|
75
|
5500
|
42
|
70
|
19
|
1005
|
| UPSS-7500-120-120-90 |
7.5
|
125
|
75
|
6800
|
42
|
70
|
19
|
1175
|
| UPSS-10000-120-120-90 |
10
|
166
|
75
|
9000
|
42
|
70
|
19
|
1225
|
Mechanical Specifications Continued
|
| Model Number |
Battery
VDC
|
Battery
Ampers
|
Battery
Run Time
Minutes
|
Battery Cabinet Dimension
|
No. of
Battery
Cabs.
|
Battery
Cabinet
NetWt.
lbs.
|
|
(D)
Width
Inches
|
(E)
Height
Inches
|
(F)
Depth
Inches
|
| UPSS-1000-120-120-90 |
48
|
28
|
90
|
~
|
~
|
~
|
~
|
~
|
| UPSS-1500-120-120-90 |
48
|
43
|
90
|
~
|
~
|
~
|
~
|
~
|
| UPSS-3000-120-120-90 |
48
|
85
|
90
|
42
|
50
|
19
|
1
|
811
|
| UPSS-4500-120-120-90 |
48
|
128
|
90
|
42
|
62
|
19
|
1
|
1271
|
| UPSS-6000-120-120-90 |
48
|
170
|
90
|
42
|
62
|
19
|
1
|
1566
|
| UPSS-7500-120-120-90 |
48
|
213
|
90
|
42
|
70
|
19
|
1
|
1820
|
| UPSS-10000-120-120-90 |
60
|
227
|
90
|
42
|
62
|
19
|
2
|
1260
|
Electrical Specifications
|
|
Input
|
Output
|
| Standard Voltage: 120 VAC
+/-20%. Other voltages available on request.
Power Walk In: 2 cycles, which limits the inrush current from the utility
to 200% maximum.
Frequency: 60Hz +/-5%. (50Hz available upon request.)
Synchronizing Slew Rate: 1 Hz per second nominal.
I/O Noise Reduction: 140dB transverse mode.
Input Current: 6% at full load low line. |
Standard Voltage: 120 VAC.
Load Power Factor: .75 lag to .9 lead.
Frequency: Normally, synchronized to utility, +/-.05% during emergency
(50 Hz available upon request)
Regulation (Static): Input variations +/- 1%, load current change +/-2%,
battery+/-2%.
Regulation (Dynamic): +/-6% for a +/-25% load step change. +/-12% for a
50% load step change, recovery within 3 cycles.
Distortion: 5% THD linear load..
Overload: 130% for 5 min.
Transfer Time: None, 0ms transfer time. True-On-Line System. |
Electrical Specifications Continued
|
|
Battery
|
Physical
|
Types:
S ~ Sealed Lead Calcium
L ~ Refillable Lead Acid
N ~ Refillable NiCad
Standard Battery: Sealed lead calcium.
Charger: Automatic boost charge (equalize) is applied with a solid-state
timer for 24 hrs. approximately every 3 months. Trickle LED mode indicators
supplied on each charger..
Recharge Time: 24 Hours.
Protection: Auto low battery voltage disconnect Automatic restart upon
utility return.
Circuit Breaker: Also used as a battery isolator.
Optional Run Time: Extended run times available upon request, consult
Factory. |
Relative Humidity: 95% non-
condensing.
Operating Temperature: 32°F-104° F. Continuous operation at high or low
ambient temperatures may affect battery life and run time.
Front Panel Controls Group: Battery DC voltmeter. Output AC voltmeter.
Utility Power OK indicator. Battery charge ammend System Test Switch.
Hi-charge indicator.
Automatic Bypass Switch: Upon an inverter failure, the AC utility
automatically transfers to the load with a mechanical switch within 3
seconds. (Fast solid-state 2ms, switching upon request. SBYP Optional). |
|