  Series Features SHN
 

 

 

  • Integrated Solid State System & Switching
  • Three-Rate, Controlled, Automatic Charger ~ No manual battery recycling
  • Low Voltage Battery Cutoff
  • Brownout Sensitivity
  • Fused AC Input & DC Output Circuit Protection
  • Single Voltage Transformer for
    120 VAC Operation
  • Maximum Input Rating
    120VAC, 60 Hz, 1.0 Amps

Shown in Standard Two Tone Beige &
Cocoa Finish

The SHN Series is equipped with solid state electronics and switching circuitry which reduces component wear and dramatically extends product life. The refillable Nickel Cadmium provides 20 years of service in ambient temperatures ranging from -22 degrees to 140 degrees F.

 

  • Par-46 Sealed Beam Lamps
    STD Lamps: 6 Volt ~ 21 Watt
 

  • Refillable Nickel Cadmium Battery
  • -22 degrees ~ 140 degrees F Operating Range
  • 6 Volt Operation
  • 20-25 Year Operating Life
 

  • Rugged 20 gauge Steel Housing
  • Top End Battery Access
  • Battery Viewport
  • Full Length Piano Hinge With Lock Hasp
  • Integral Carrying Handles
  • Two Tone Powder Coat Finish (Beige & Cocoa) Standard
  • Slide Out Control Chassis
  • Test Switch
  • Load Cutoff Switch
  • Voltmeter
  • Amber (Power On), Red (Hi-Charge), & Green (Trickle Charge) LED Indicator
  • UL Listed
 
Height: 20.5"
Width: 18.5"
Depth: 8.5"

 

  Use No. 22 Mounting Shelf  

Unit Information (Watts per hour)

 

Model #

 

STD LAMP WATT

 

1.5

 

2

 

3

 

4

 

5

 

6

 

7

 

8

 

Replacement Battery

2SH6N40  

21

 

96

 

75

 

48

 

36

 

28

 

23

 

20

 

18

 

(1) N640

2SH6N50  

21

 

120

 

96

 

60

 

48

 

39

 

30

 

28

 

24

 

(1) N650

Illumination is rated to 87.5% of nominal system voltage and recharge to full capacity within 24 hours.
NEC requires 1.5 hours of emergency illumination.

 

Warranty

Factory Options

-GY Industrial Grey Finish
-P2 Cord & Plug for 120 VAC Input

Ordering Information

 

2
Lamp Heads on Unit

 

SH
Series

 

6
DC Battery Voltage

 

N
Battery Type
N~NiCd

 

40
Battery
Amp/Hour

 

-P2
Options

 

 

Home Batteries  UPS Technology Emergency Lighting Battery Chargers Factory Links Contact Us Buy Batteries Online

Power Factor Inc.

2526 Manana Dr – Suite 102 – Dallas – Texas – 75220

 Our Goal, NO DISSATISFIED CUSTOMERS!

Since 1995

While every precaution has been taken to ensure accuracy and completeness in this literature, Power Factor Inc. assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.