| Standard Voltage: 120 VAC+/-
10- 15% except 16.7 kVA (277 VAC). Other voltages available on request.
Power Walk In: 2 cycles, which limits the inrush current from the utility
to 125% maximum.
Frequency: 60Hz +/-3%. 50Hz available upon request.
Input Transfer Voltage: Brownout, Transfer to inverter @85% utility input
voltage. Transfer back to utility @ 90% input voltage. |
Standard Voltage: 120 VAC
except 16.7 kVA (277 VAC). Other voltages available on request.
Output regulation during emergency (static): Load current changes +/-4%,
battery discharge +/-4%.
Output regulation during emergency (Dynamic): +/-3% for a +/-25% load
step change. +/-6% for a 50% load step change, recovery within 3 cycles.
Load Power Factor: .75 lag to .9 lead.
Output Frequency: +/-1% during emergency.
Output Distortion: 10% THD linear load.
Overload: Normal: 150% for 5 min. Emergency: 130% for 5 min. Transfer
Time: 50 ms. |