Batteries UPS Technology Emergency Lighting Battery Chargers TVSS 9 Power Problems Olight Flashlights Problems with Power Factory Links Contact Us
EFB Series GA Series HE Series IL Series IQ Series LT Series PHE Series S6L Series SHL Series SHN Series TCL Series TCS Series
800-706-7009
| |
| |
Meets or exceeds UL specifications for use in the following areas:
- Class I, Div. I Groups C & D
- Class II, Div. I, Groups E, F, & G
- Class III
|
Designed for use in hazardous and potentially hazardous environments, the
HE Series offers completely self-contained unit operaton with extended lamp
run times. |
|

|
- Integrated Solid State System
- Controlled, automatic Charger ~ No manual battery recycling
- Dual Voltage Transformer for
120/277 VAC Operation
|
|

|
- Sealed Nickel Cadmium Battery [N] on 30 & 50 Watt Units
- Sealed Pure Lead Batery [P] on 85 Watt Unit
- 6 or 12 Volt Operation
- Maintenance Free
|
|

|
- Completely Self-Contained Operation
- Heavy Cast, Copper-Free Aluminum Housing
- Sealed, Bottom Mounted Test Switch
- Power On Indicator
- UL 844, 924, & 1203 Listed
|
| Height: |
12.0" |
| Width: |
15.0" |
| Depth: |
8.8" |
|
| |
|
|
Unit Information (Watts per hour)
|
Model #
|
STD LAMP WATT
|
1.5
|
2
|
3
|
Replacement Battery
|
| HE6N8 |
~
|
30
|
23
|
11
|
(1) N68
|
| HE6P36 |
~
|
85
|
64
|
43
|
(1) P636
|
| HE12N20 |
~
|
50
|
38
|
25
|
(1) N1220
|
Illumination is rated to 87.5% of nominal system voltage
and recharge to full capacity within 24 hours.
NEC requires 1.5 hours of emergency illumination.
Ordering Information
|
HE
Series
|
6
DC Battery Voltage
|
N
Battery Type
(N~NiCd)
|
8
Battery
Amp/Hour
|
|