| Standard Input Voltage:
120/208 VAC 3-phase, 4-wire, +10%-15%. Other voltages available on request.
Input Power Walk In: 2 cycles, which limits the inrush current from the
utility to 125% maximum.
Input Frequency: 60Hz +/- 3%. (50Hz available upon request).
Synchronizing Slew Rate: 1 Hz per second nominal.
Input Lightning Protection: Up to 10,000V, 320 joules, meets IEEE 587.
I/O Noise Reduction: 80dB transverse mode, 120 dB common mode.
Input Current Distortion: 6% at full load nominal line.
Input Circuit Breaker: For complete system protection. |
Standard Output Voltage:
120/208 VAC, 3-phase, 4-wire. Other voltages available on request.
Output Regualtion (Static): Input variations +/- 1%, load current change
+/-2%, battery +/-2%.
Output Regulation (Dynamic): +/-3% for a +/-25% load step change. +/-6%
for a 50% load step change, recovery within 3 cycles.
Load Power Factor: .75 lag to .9 lead.
Output Frequency: Normally, synchronized to utility, +/-.05% during
emergency (50 Hz available upon request)
Output Distortion: 5% THD linear load..
Line to Line Voltage Unbalance: +/-4% for a 30% line to line load
unbalance.
Overload: Normal: 150% for 5 min. Emergency: 130% for 5 min. |