Back Up Home Batteries  UPS Technology Emergency Lighting Battery Chargers Factory Links Contact Us Buy Batteries Online

Established 1996                              Call us 800-706-7009

.
• Home • GP Series • GPL Series • EVH Series • EVX Series • HC Series • HR Series • HRL Series • MSJ Series • MSV Series • MU Series • TPL Series • UPS Series • XHRL Series • XTV Series •

.

 

Click here to Buy batteries online

Batteries
Eaton Showcase
UPS Technology
Emergency Lighting
Battery Chargers
TVSS
9 Power Problems
Olight Flashlights
Problems with Power
Factory Links
Contact Us

XHRL12360W
XHRL12410W
XHRL12475W
XHRL12620W

800-706-7009

 

A+ Rating with the Better Business Bureau

• XHRL12360W • XHRL12410W • XHRL12475W • XHRL12620W •

CSB China Storage Battery XHRL12620W XHRL-12620W  12 Volt 620WPC (Watts Per Cell) Battery

 

XHRL12620W
12 V 620.0w/cell
XHRL12620 battery is specially designed for high-rate discharge applications. service life is up to 10 years in standby use, or more than 260 cycles at 100% discharge.
 
Download : XHRL12620W Spec Sheet -(1.28M)
     
 
Specification  
Cells Per Unit 6
Voltage Per Unit 12 V
Capacity 620.0W@ 15 Minute-Rate to 1.67V Per Cell @ 25°C(77°F)
Weight Approx. 47.2 kg(100.75 lbs)
Maximum Discharge Current 800A(5sec)
Internal Resistance Approx. Approx. 3.7 mΩ
Operating Temperature Range Discharge:-20℃~50℃(-4°F~122°F)
Charge:-20℃~50℃(-4°F~122°F)
Storage:-15℃~40℃(5°F~104°F)
Nominal Operating Temperature Range 25°C±3°C(77°F±5°F)
Float Charging Voltage 13.5 to 13.8 VDC/Unit Average at 25°C(77°F)
Recommended Maximum Charging Current Limit 62 A
Equalization and Cycle Service 14.4 to 15.0 VDC/Unit Average at 25°C(77°F)
Self Discharge CSB Batteries can be stored for more than 6 months at 25℃(77°F). Please charge batteries before using. For higher temperatures the time interval will be shorter.
Terminal I2-Thread lead alloy recessed terminal to accept M6/M8 bolt
Container Material PPE(UL94-V0/File161759)*Flammability resistance can
be available upon request.

 
Dimensions  


 
Constant Current Discharge Characteristics Unit:Amperes (25°C,77°F)
F.V/Time 2MIN 4MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V 766.00 641.00 571.00 504.00 458.00 349.00 283.00 206.00 116.00 81.70
1.67V 660.00 585.00 511.00 466.00 420.00 326.00 273.00 200.00 114.00 79.80
1.70V 622.00 545.00 486.00 448.00 398.00 315.00 267.00 196.00 113.00 78.30
1.75V 553.00 485.00 449.00 398.00 356.00 293.00 252.00 188.00 110.00 78.20
1.80V 494.00 443.00 383.00 344.00 315.00 270.00 229.00 175.00 106.00 75.60
1.85V 437.00 360.00 322.00 298.00 280.00 239.00 201.00 158.00 97.90 71.10
Constant Power Discharge Characteristics Unit:Watts (25°C,77°F)
F.V/Time 2MIN 4MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V 7070.00 6088.00 5529.00 5280.00 4692.00 3770.00 3108.00 2304.00 1344.00 966.00
1.67V 6439.00 5680.00 5432.00 4894.00 4387.00 3720.00 2983.00 2249.00 1329.00 959.00
1.70V 6090.00 5494.00 5336.00 4692.00 4262.00 3540.00 2918.00 2222.00 1325.00 957.00
1.75V 5579.00 5208.00 4825.00 4311.00 3969.00 3282.00 2742.00 2135.00 1293.00 944.00
1.80V 5235.00 4660.00 4246.00 3894.00 3639.00 2956.00 2515.00 2017.00 1247.00 916.00
1.85V 4134.00 3765.00 3674.00 3470.00 3120.00 2576.00 2257.00 1864.00 1163.00 867.00

CSB China Storage Battery XHRL12620W XHRL-12620W  12 Volt 620WPC (Watts Per Cell) Battery CSB China Storage Battery XHRL12620W XHRL-12620W  12 Volt 620WPC (Watts Per Cell) Battery CSB China Storage Battery XHRL12620W XHRL-12620W  12 Volt 620WPC (Watts Per Cell) Battery CSB China Storage Battery XHRL12620W XHRL-12620W  12 Volt 620WPC (Watts Per Cell) Battery CSB China Storage Battery XHRL12620W XHRL-12620W  12 Volt 620WPC (Watts Per Cell) Battery

• XHRL12360W • XHRL12410W • XHRL12475W • XHRL12620W •

 

 

 

 

Home Batteries  UPS Technology Emergency Lighting Battery Chargers Factory Links Contact Us Buy Batteries Online

Power Factor Inc.

2526 Manana Dr – Suite 102 – Dallas – Texas – 75220

800-706-7009

 Our Goal, NO DISSATISFIED CUSTOMERS!

Since 1995

While every precaution has been taken to ensure accuracy and completeness in this literature, Power Factor Inc. assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.