Home Up HR1221W HR1224W HR1234W HR1251W HR1290W HR12120W.

CSB China Storage Battery HR1234W HR-1234W  12 Volt 34 Watt per cell 9 AH Battery  

Click here to purchase the HC1234W Battery from our online store at batteriesasap.com

HR Series
HR1234W
12 V 34.0w/cell
HR 1234WF2 is specially designed for high efficient discharge application. Its characteristics are small volume, light weight and high discharge efficiency. It can be used for more than 260 cycles at 100% discharge in cycle service, up to 5 yeas in standby service.
 
Download : HR1234 Spec Sheet-(614.5K)
 

 

Specification  
Cells Per Unit 6
Voltage Per Unit 12 V
Capacity 34W @ 15 minute-rate to 1.67V per cell @ 25°C (77°F)
Weight Approx. 2.50kg. (5.51lbs.)
Maximum Discharge current 130A (5sec.)
Internal Resistance Approx. Approx. 19mΩ
Operating Temperature Range Discharge:-15℃~50℃(5°F~122°F)
Charge:-15℃~40℃(5°F~104°F)
Storage:-15℃~40℃(5°F~104°F)
Nominal Operating Temperature Range 25°C ± 3°C (77°F ± 5°F)
Float charging voltage 13.5 to 13.8 VDC/unit Average at 25°C (77°F)
Recommended Maximum Charging current limit 3.4A
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at 25°C (77°F)
Self Discharge CSB Batteries can be stored for more than 6 months at 25°C (77°F) Please charge batteries before using. For higher temperatures the time interval will be shorter.
Terminal F1/F2-Faston Tab187/250
Container Material ABS(UL94-HB/File E50263)*Flammability resistance of(UL94-V0/File E88367) can be available upon request.

 

Dimensions  
Volt 12
Amps 9
Length 5.94
Width 2.56
Height 3.7
Terminals F2
Weight (6.2)
Manufacturer CSB
Model # HR1234WF2 CSB 12V 9Ah

 

Constant Current Discharge Characteristics Unit:Amperes (25℃,77℉)
F.V/Time 2MIN 4MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V 73.84 49.16 36.83 29.74 25.39 18.49 14.57 10.54 5.98 4.24
1.67V 65.84 44.80 34.40 28.21 24.15 17.80 14.08 10.27 5.86 4.15
1.70V 62.23 42.90 33.30 27.47 23.60 17.42 13.84 10.14 5.80 4.11
1.75V 56.25 39.80 31.60 26.20 22.67 16.80 13.47 9.90 5.69 4.04
1.80V 50.26 36.40 29.70 24.87 21.66 16.23 13.12 9.66 5.59 3.98
1.85V 43.25 32.87 27.63 23.45 20.65 15.59 12.71 9.38 5.50 3.91
Constant Power Discharge Characteristics Unit:Watts (25℃,77℉)
F.V/Time 2MIN 4MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V 705.86 505.50 394.70 327.54 286.26 210.75 169.34 124.09 71.65 50.84
1.67V 645.30 470.00 376.40 314.50 275.50 204.70 165.00 121.30 70.52 50.05
1.70V 618.20 454.00 365.50 308.00 270.10 201.60 163.10 119.90 70.00 49.64
1.75V 571.30 426.00 350.00 296.40 260.00 196.20 159.50 118.00 69.00 49.00
1.80V 523.50 400.00 333.00 284.50 250.40 191.10 155.80 116.20 68.09 48.34
1.85V 478.32 375.59 315.69 273.06 241.41 186.11 152.32 113.96 67.02 47.66

CSB China Storage Battery HR1234W HR-1234W  12 Volt 34 Watt per cell 9 AH Battery   CSB China Storage Battery HR1234W HR-1234W  12 Volt 34 Watt per cell 9 AH Battery   CSB China Storage Battery HR1234W HR-1234W  12 Volt 34 Watt per cell 9 AH Battery   CSB China Storage Battery HR1234W HR-1234W  12 Volt 34 Watt per cell 9 AH Battery   CSB China Storage Battery HR1234W HR-1234W  12 Volt 34 Watt per cell 9 AH Battery  

Home Up HR1221W HR1224W HR1234W HR1251W HR1290W HR12120W

 

 


 

 

 

Home Batteries  UPS Technology Emergency Lighting Battery Chargers Factory Links Contact Us Buy Batteries Online

Power Factor Inc.

2526 Manana Dr – Suite 102 – Dallas – Texas – 75220

800-706-7009

 Our Goal, NO DISSATISFIED CUSTOMERS!

Since 1995

While every precaution has been taken to ensure accuracy and completeness in this literature, Power Factor Inc. assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.