Problems with Power
Factory Links
Contact Us

HR1221W
HR1224W
HR1234W
HR1251W
HR1290W
HR12120W

.

CSB China Storage Battery HR12120W HR-12120W  12 Volt 120 Watt per cell 30 AH Battery  

Click here to purchase the HC12120W Battery from our online store at batteriesasap.com

HR Series
HR12120W
12 V 120.0w/cell
HR 12120W is designed specially for high efficient discharge application. It\'s characteristics are small volume, light weight and high discharge efficiency. It can be used for more than 260 cycles at 100% discharge in cycle service, up to 5 years in standby service.
 
Download : HR12120 Spec Sheet-(620.16K)
 

 

Specification  
Cells Per Unit 6
Voltage Per Unit 12 V
Capacity 120W @ 15 minute-rate to 1.67V per cell @ 25°C (77°F)
Weight Approx. 10.2 Kg (22.49 LBS)
Maximum Discharge current 400A (5 Sec)
Internal Resistance Approx. Approx. 9 mΩ
Operating Temperature Range Discharge:-15℃~50℃(5°F~122°F)
Charge:-15℃~40℃(5°F~104°F)
Storage:-15℃~40℃(5°F~104°F)
Nominal Operating Temperature Range 25°C ± 3°C (77°F ± 5°F)
Float charging voltage 13.5 to 13.8 VDC/Unit Average at 25°C (77°F)
Recommended Maximum Charging current limit 12.0 A
Equalization and Cycle Service 14.4 to 15.0 VDC/Unit Average at 25°C (77°F)
Self Discharge CSB Batteries can be stored for more than 6 months at 25°C (77°F). Please charge batteries before using. For higher temperatures the time interval will be shorter.
Terminal I1-Thread lead alloy recessed terminal to accept M5 bolt
Container Material ABS(UL94-HB/File E50263)*Flammability resistance of(UL94-V0/File E88367) can be available upon request.

 

Dimensions  
Volt 12
Amps 30
Length 6.53
Width 4.92
Height 6.55
Terminals TI
Weight (24.3)
Manufacturer CSB
Model # HR12120WFR CSB 12V 30Ah

 

Constant Current Discharge Characteristics Unit:Amperes (25℃,77℉)
F.V/Time 2MIN 4MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V 169.40 147.91 124.73 107.15 94.18 70.46 56.10 41.20 24.45 16.84
1.67V 152.90 135.20 114.55 100.00 88.92 66.98 53.60 39.68 23.99 16.61
1.70V 145.80 128.00 109.30 95.49 85.60 65.31 52.50 39.20 23.66 16.43
1.75V 131.90 116.68 100.69 88.92 80.16 62.00 50.40 37.84 23.07 16.15
1.80V 117.00 104.71 91.20 81.28 73.28 58.34 47.99 35.99 22.20 15.76
1.85V 100.00 92.46 82.41 74.30 67.29 54.32 45.70 34.59 21.18 15.22
Constant Power Discharge Characteristics Unit:Watts (25℃,77℉)
F.V/Time 2MIN 4MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V 1744.82 1621.81 1419.05 1199.49 1030.38 770.90 620.86 462.18 284.36 196.89
1.67V 1608.32 1495.00 1315.00 1119.00 975.00 737.90 599.79 453.04 279.20 194.00
1.70V 1539.00 1427.00 1260.00 1084.00 947.00 724.43 590.00 447.00 276.30 192.80
1.75V 1412.00 1306.00 1161.00 1012.00 895.36 700.76 578.00 435.25 270.39 190.00
1.80V 1273.00 1181.29 1060.00 944.00 853.10 676.08 561.04 418.39 262.90 186.40
1.85V 1100.00 1044.81 966.05 877.00 805.37 647.83 535.79 401.72 252.92 181.42


 

 

Home Batteries  UPS Technology Emergency Lighting Battery Chargers Factory Links Contact Us Buy Batteries Online

Power Factor Inc.

2526 Manana Dr – Suite 102 – Dallas – Texas – 75220

800-706-7009

 Our Goal, NO DISSATISFIED CUSTOMERS!

Since 1995

While every precaution has been taken to ensure accuracy and completeness in this literature, Power Factor Inc. assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.