Home • Up • GP613 • GP633 • GP640 • GP645 • GP670 • GP690 • GP6110 • GP1213 • GP1222 • GP1245 • GP1270 • GP12110 • GP12170 • GP12200 • GP12260 • GP12340 • GP12400 • GP24150 • GP24170 • GP12650 • GP121000 • EVX1272 • EVX12120 • EVX12170 • EVX12200 • EVX12260 • EVX12300 • EVX12340 • EVX12400 • EVX12520 • EVX12650 • EVX12750 • EVX121000 • HC1217W • HC1221W • HC1225W • HC1228W • HR1221W • HR1224W • HR1234W • HR1251W • HR1290W • HR12120W

 

 

Contact Us Toll Free

Buy batteries on-line

Request Info

UPS Systems

Universal Battery Valve Regulated Lead Acid Batteries Batteries

  Emergency Lighting

Battery chargers, rectifiers, dc power systems by SENS Battery Chargers

Click for more about the Battery Rack™ 20 with Tester (Grey) Battery Storage

Specials!

Service

Lease Info

 

CSB China Storage Battery HC1228W HC-1228W  12 Volt 28 Watt per cell 8.2 AH Battery  

Click Here to Buy On-Line the HC1228W

HC Series
HC1228W
12 V 28.0w/cell
HC1228W is specially designed for high efficient discharge application. Its invisible terminal can be inserted PC board directly. HC series battery can serve more than 260 cycles at 100% discharge in cycle service, up to 5 years in standby service.
 
Download : HC1228 Spec Sheet-(619.65K)
 
 

 

Specification  
Cells Per Unit 6
Voltage Per Unit 12 V
Capacity 28W @ 15 minute-rate to 1.67V per cell @ 25°C (77°F)
Weight Approx. 2.51kg. (5.53 lbs.)
Maximum Discharge current 60A (5sec.)
Internal Resistance Approx. Approx. 21mΩ
Operating Temperature Range Discharge:-15℃~50℃(5°F~122°F)
Charge:-15℃~40℃(5°F~104°F)
Storage:-15℃~40℃(5°F~104°F)
Nominal Operating Temperature Range 25°C ± 3°C (77°F ± 5°F)
Float charging voltage 13.5 to 13.8 VDC/unit Average at 25°C (77°F)
Recommended Maximum Charging current limit 2.8A
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at 25°C (77°F)
Self Discharge CSB Batteries can be stored for more than 6 months at 25°C (77°F) Please charge batteries before using. For higher temperatures the time interval will be shorter.
Terminal C1-Faston Tab187/250
Container Material ABS(UL94-HB/File E50263)*Flammability resistance of(UL94-V0/File E88367) can be available upon request.


 

Dimensions  



 

Constant Current Discharge Characteristics Unit:Amperes (25℃,77℉)
F.V/Time 2MIN 4MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V 48.58 38.17 31.25 27.17 23.33 17.98 14.92 11.58 7.32 4.75
1.67V 46.94 36.80 30.19 26.33 22.70 17.52 14.69 11.46 7.26 4.58
1.70V 45.19 35.44 29.33 25.45 22.07 17.04 14.44 11.36 7.18 4.43
1.75V 43.35 34.03 28.20 24.54 21.39 16.64 14.21 11.26 7.11 4.28
1.80V 41.41 32.58 27.08 23.61 20.76 16.29 14.01 11.18 7.02 4.14
1.85V 39.38 30.91 25.95 22.69 20.13 15.95 13.80 11.09 6.91 3.99
Constant Power Discharge Characteristics Unit:Watts (25℃,77℉)
F.V/Time 2MIN 4MIN 6MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V 583.00 458.00 375.00 326.00 280.00 211.83 175.38 139.00 89.53 57.00
1.67V 563.40 441.60 361.20 315.00 272.50 207.20 172.50 137.75 88.63 55.11
1.70V 544.10 425.20 348.90 304.00 264.70 202.10 169.90 136.50 87.73 53.20
1.75V 521.90 407.80 336.70 292.60 257.50 197.20 166.90 135.30 86.83 51.45
1.80V 498.10 391.00 325.00 280.00 248.00 192.75 164.05 134.17 85.96 49.70
1.85V 472.50 371.00 311.50 267.50 238.50 187.49 161.43 133.00 85.11 47.95


 

Home - 9 Power Problems - Problems with Power - APC - Powerware - MinuteMan - MGE - Liebert - Batteries - Chargers / Rectifiers - Emergency Lighting - Service - Factory Links

 Contact Us

Power Factor Inc.

2526 Manana Dr – Suite 102 – Dallas – Texas – 75220

NO DISSATISFIED CUSTOMERS!

Since 1995

While every precaution has been taken to ensure accuracy and completeness in this literature, Power Factor Inc. assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.