800-706-7009

 

Home • Up • GP613 • GP633 • GP640 • GP645 • GP670 • GP690 • GP6110 • GP1213 • GP1222 • GP1245 • GP1270 • GP12110 • GP12170 • GP12200 • GP12260 • GP12340 • GP12400 • GP24150 • GP24170 • GP12650 • GP121000 • EVX1272 • EVX12120 • EVX12170 • EVX12200 • EVX12260 • EVX12300 • EVX12340 • EVX12400 • EVX12520 • EVX12650 • EVX12750 • EVX121000 • HC1217W • HC1221W • HC1225W • HC1228W • HR1221W • HR1224W • HR1234W • HR1251W • HR1290W • HR12120W

 

 

Contact Us Toll Free

Buy batteries on-line

Request Info

UPS Systems

Universal Battery Valve Regulated Lead Acid Batteries Batteries

  Emergency Lighting

Battery chargers, rectifiers, dc power systems by SENS Battery Chargers

Click for more about the Battery Rack™ 20 with Tester (Grey) Battery Storage

Specials!

Service

Lease Info

 

 

CSB China Storage Battery GP12650 GP-12650  12 Volt 65 Amp Hr. ( AH ) Battery  

Click Here to Buy On-Line

GP Series
GP12650
12 V 65.0Ah
GP 12650 is a general purpose battery up to 5 years in standby service or more than 260 cycles at 100% discharge in cycle service.
As with all CSB batteries, all are rechargeable, highly efficient, leak proof and maintenance free.
 
Download : GP12650 Spec Sheet-(697.46K)
 

 

Specification  
Cells Per Unit 6
Voltage Per Unit 12 V
Capacity 65 Ah @ 20hr-rate to 1.75V per cell @ 25°C (77°F)
Weight (kg) Approx. 20.0kg. (44.09 lbs.)
Maximum Discharge current (A) 500A (5sec.)
Internal Resistance Approx. Approx. 6 mΩ
Operating Temperature Range Discharge:-15℃~50℃(5°F~122°F)
Charge:-15℃~40℃(5°F~104°F)
Storage:-15℃~40℃(5°F~104°F)
Nominal Operating Temperature Range 25°C ± 3°C (77°F ± 5°F)
Float charging voltage 13.5 to 13.8 VDC/unit Average at 25°C (77°F)
Recommended Maximum Charging current limit 19.5A
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at 25°C (77°F)
Self Discharge CSB Batteries can be stored for more than 6 months at 25°C (77°F) Please charge batteries before using. For higher temperatures the time interval will be shorter.
Terminal B4-L terminal to accept M6 nut & bolt
Container Material Polypropylene(UL 94-V0/File E50955)*Flammability resistance of (UL 94-HB/File E216959) can be available upon request.


 

Dimensions  



 

Constant Current Discharge Characteristics Unit:Amperes (25℃,77℉)
F.V/Time 5MIN 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V 270.83 173.33 131.67 79.92 47.17 27.25 19.40 15.08 12.40 8.08 6.58 3.57
1.67V 241.66 161.66 124.40 78.28 46.86 27.19 19.29 15.02 12.29 7.97 6.47 3.42
1.70V 229.17 156.67 121.40 77.26 46.70 27.10 19.20 14.90 12.20 7.93 6.43 3.36
1.75V 207.50 146.67 116.66 75.36 46.37 27.00 19.10 14.80 12.10 7.86 6.32 3.25
1.80V 185.83 136.67 110.83 73.42 45.92 26.90 19.00 14.70 12.00 7.76 6.21 3.14
1.85V 164.16 126.67 104.99 71.34 45.38 26.80 18.90 14.60 11.90 7.66 6.10 3.03
Constant Power Discharge Characteristics Unit:Watts (25℃,77℉)
F.V/Time 5MIN 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V 3250.00 2080.00 1580.00 959.00 566.00 327.00 232.00 181.00 148.00 97.00 79.00 40.90
1.67V 2900.00 1940.00 1503.00 935.00 562.00 326.30 231.30 180.30 147.30 95.95 77.67 39.15
1.70V 2750.00 1871.00 1460.00 924.20 559.60 325.00 230.00 179.00 146.00 95.50 77.10 38.40
1.75V 2490.00 1760.00 1400.00 902.50 555.40 324.00 229.00 178.00 145.00 94.30 75.80 37.05
1.80V 2230.00 1640.00 1330.00 881.00 550.40 323.00 228.00 177.00 144.00 93.10 74.50 35.70
1.85V 1970.00 1520.00 1260.00 856.00 544.50 322.00 227.00 176.00 143.00 91.90 73.20 34.35


 

Home - 9 Power Problems - Problems with Power - APC - Powerware - MinuteMan - MGE - Liebert - Batteries - Chargers / Rectifiers - Emergency Lighting - Service - Factory Links

 Contact Us

Power Factor Inc.

2526 Manana Dr – Suite 102 – Dallas – Texas – 75220

NO DISSATISFIED CUSTOMERS!

Since 1995

While every precaution has been taken to ensure accuracy and completeness in this literature, Power Factor Inc. assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.